Inspections for the day of: Monday, August 14, 2006.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-02774 Final8/11/20068/14/20068/14/2006 4:45:54 PMPPASS
Ready for final, please call Dan, thank you; Phone #: ###-#### Internet Inspection Request from: Wendy Waters ok to final
ELE06-00091 Final8/13/20068/14/20068/14/2006 4:24:22 PMPFAIL
Phone #: ###-#### Internet Inspection Request from: steve creswell called, left message, left corr notice, nec 210.8(A)(C) island recpt shall be gfci protected,422.31(B) dishwasher shll have lockout, 410.6 luminaire shall be installed in dining room closet, 406.4(D) recpt face shall be flush with or project from faceplate, 406.5 recpt faceplates shall seat against finished surface, and be supplied at water softener and hw heater area, BCC dome over stairs shall be covered or finished, outside rear recpt shall operate correctly
ELE06-02057 ELE-Aging Inspection8/14/20068/14/20068/14/2006 3:59:54 PM NR
called, suc
ELE06-00921 ELE-Aging Inspection8/14/20068/14/20068/14/2006 3:19:12 PM DONE
called, working on getting field evauation for generator, Generator apparently not connected per elect.
ELE06-01882 Final8/14/20068/14/20068/14/2006 3:03:43 PMPPASS
Work performed by Greg Fanrworth.; Phone #: ###-#### Internet Inspection Request from: Matt Santacruz ok to final
ELE06-02926 Final8/14/20068/14/20068/14/2006 1:32:07 PMPPASS
need inspection @ space #5 to get power turned back on.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH see p/s ok to final
ELE06-02926 Permanent Service8/14/20068/14/20068/14/2006 1:31:38 PMPPASS
need inspection @ space #5 to get power turned back on.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH corr made, p/s o/h rec ok
ELE06-02926 Final8/14/20068/14/20068/14/2006 1:29:45 PMPPASS
need inspection @ space #5 to get power turned back on.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH corr made, p/s o/h rec ok
ELE06-02968 Permanent Service8/14/20068/14/20068/14/2006 12:40:01 PMPPASS
brad; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr to provide abrasion protection for gec, p/s u/g rec ok
ELE06-02823 Final8/11/20068/14/20068/14/2006 11:54:09 AMAPASS
Internet Inspection Request from: Tyler Bowen corr made, ok to final
ELE06-02980 Rough-In Permanent Service8/11/20068/14/20068/14/2006 9:25:26 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Alan Lusk called contr to chg recpt location up bedroom, add recpt in kitchen, finish make-up, change room count to 20 rooms, ok to pour gec, told to call for inspection before backfill gec, ric ok, p/s u/g n ok
ELE06-02967 Rough-In Permanent Service8/10/20068/14/20068/14/2006 9:21:34 AMAPASS
adam; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr, left survey, BCC all make-up shall be done-front and rear lights and recpts plus 2 boxes in kitchen, box for hw heater, ric ok, p/s o/h n ok