FIR05-00525
| FIR-Aging Inspection | 8/14/2006 | 8/14/2006 | 8/15/2006 10:44:43 AM | | DEFR |
|
|
|
FIR06-00565
| INSP-Final Inspection | 8/14/2006 | 8/14/2006 | 8/14/2006 4:18:20 PM | P | NR |
|
|
The hood suppression system is not completed to allow a full functional test.
|
FIR06-00593
| INSP-Final Inspection | 8/11/2006 | 8/14/2006 | 8/14/2006 4:15:30 PM | A | FAIL |
|
|
Gas supply is not completed to allow functional testing of the suppression system, also missing K class extinguisher and bulbs in the hood lights to verify power shutoff, inspection stopped at this time.
|
FIR06-00565
| INSP-Final Inspection | 8/10/2006 | 8/14/2006 | 8/14/2006 4:12:49 PM | A | NR |
|
|
Gas supply connection is not completed to enable testing of the suppression system.
|
MIS06-00197
| FIR-Final | 8/11/2006 | 8/14/2006 | 8/14/2006 11:33:43 AM | A | FAIL |
|
|
Need to repair the non-functional exit sign/emergency light at the main entry exit, provide and post max occupant load sign.
|
BLD05-01077
| FIRE-Conference | 8/10/2006 | 8/14/2006 | 8/14/2006 10:26:30 AM | A | DONE |
|
|
On site confrence to discuss occupancy requirements for the fourth floor parking area.
|
FIR05-00901
| INSP-Sprinkler Rough-in/Hydro | 8/11/2006 | 8/14/2006 | 8/14/2006 8:49:08 AM | A | CANC |
|
|
Leroy stated that this was a hydro but final. His # ###-####. Thanks; Phone #: ###-#### Internet Inspection Request from: Trent Bice Inspection cancelled from web by: Trent Bice
|