Inspections for the day of: Tuesday, August 14, 2007.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-02662 Electrical Rough-In8/14/20078/14/20078/14/2007 2:45:23 PMPPART
Mike; Phone #: ###-#### Internet Inspection Request from: Hattie James; swimming pool bonding e grid and diving board and handrails ok
ELE07-02579 Final8/13/20078/14/20078/14/2007 2:28:46 PMPPASS
final inspection on swimming pool Phone #: ###-#### Internet Inspection Request from: Jari Rivers ok card signed
ELE07-01455 Permanent Service8/14/20078/14/20078/14/2007 1:46:44 PMPPASS
WARREN WING - HE WILL MEET @ JOBSITE Phone #: ###-#### Internet Inspection Request from: Randy Vail
p/s u/g new ok
ELE07-02831 Conference8/14/20078/14/20078/14/2007 1:12:51 PMPDONE
please call prior to inspection so he can meet ya there--Terry ###-#### ok wiring for shed
ELE07-00780 Final8/13/20078/14/20078/14/2007 12:48:40 PMPPASS
Phone #: ###-#### Internet Inspection Request from: ERIC CENTERS survey posted 210.8(B)(2) needs gfci for refer and freezer recepts called final ok c ard signed
ELE07-02381 Final8/13/20078/14/20078/14/2007 10:35:44 AMAPASS
Any questions or concerns please call Clay at ###-####. Thanks. Phone #: ###-#### Internet Inspection Request from: Clay Morgan ok
ELE07-02822 Rough-In Permanent Service8/13/20078/14/20078/14/2007 10:10:09 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Paul called
survey posted 210.52(A) MB needs outlet within 6ft of fixed panel of slider, protect cables 6ft of attic access r/i p/s u/g new ok
ELE07-01936 Electrical Rough-In8/13/20078/14/20078/14/2007 9:24:56 AMAPART
ted - area 2 ceiling Phone #:
ok anop
ELE07-02342 Electrical Rough-In8/13/20078/14/20078/14/2007 8:41:20 AMAFAIL
rough-in for walls. Call Todd if any problems Phone #: ###-#### Internet Inspection Request from: Tracy Robertson
corr. met contr. 600.5 shall provide required sign circuit, 300.4 (A)(1)&(D) nail plates and 11/4" for cables parallel to studs, 110.26(F)(2) remove sprinkler wiring from below outside panel, 110.12(A) seal KO subpanel, do not cover posted
ELE07-02547 Electrical Rough-In8/14/20078/14/20078/14/2007 8:06:02 AMAPART
Contact is Perry. Ceiling inspection in Electronics Dept. Phone #: ###-#### Internet Inspection Request from: David
stub wall west , front ceiling area ok