ELE07-02824
| Temporary Service | 8/14/2007 | 8/14/2007 | 8/14/2007 5:23:41 PM | P | PASS |
|
|
roger Phone #: ###-#### t/s o/h n ok
|
ELE07-02826
| Electrical Rough-In | 8/14/2007 | 8/14/2007 | 8/14/2007 5:22:20 PM | P | PASS |
|
|
roger Phone #: ###-#### ok cover ri
|
ELE07-02814
| Electrical Rough-In | 8/14/2007 | 8/14/2007 | 8/14/2007 4:30:09 PM | P | PASS |
|
|
please check spacing on conduits underground. Bob looked at pipe runs this morning, just wanted to see some stakes installed to get some space on pipes. thanks Loren Phone #: ###-#### Internet Inspection Request from: Loren Ramsey ok cover under ground conduit
|
ELE07-02786
| Final | 8/14/2007 | 8/14/2007 | 8/14/2007 3:52:10 PM | P | FAIL |
|
|
Brian, please call 1st for access; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt no service bonding to water system & service needs grounding choke for grounding electrode. note wrong type inspection should have been for per. service.
|
ELE07-02816
| Permanent Service | 8/13/2007 | 8/14/2007 | 8/14/2007 3:03:05 PM | P | PASS |
|
|
Could this possibly be scheduled for late afternoon? Phone #: ###-#### Internet Inspection Request from: Trent Reagan p/s o/h reconnect ok note sub panel temp for now they are relocating it later. they will call for final or ri when ready
|
ELE07-02660
| Final | 8/14/2007 | 8/14/2007 | 8/14/2007 1:54:14 PM | P | PASS |
|
|
the shell is ready for a final inspection please call Brad if any questions thanks Phone #: ###-#### Internet Inspection Request from: Brad Baker ok final note signed card
|
ELE07-02549
| Final | 8/13/2007 | 8/14/2007 | 8/14/2007 1:01:08 PM | A | PASS |
|
|
WAYNE NOTE: COVER Phone #: ###-#### ok final
|
ELE07-02549
| Electrical Rough-In | 8/13/2007 | 8/14/2007 | 8/14/2007 1:00:43 PM | A | PASS |
|
|
WAYNE NOTE: COVER Phone #: ###-#### ok cover ceiling
|
ELE07-02553
| Rough-In Permanent Service | 8/13/2007 | 8/14/2007 | 8/14/2007 12:02:52 PM | A | PASS |
|
|
Trent; Phone #: ###-#### ok cover ceiling p/s u/g n meter ok
|
ELE07-02548
| Final | 8/13/2007 | 8/14/2007 | 8/14/2007 11:14:53 AM | A | PASS |
|
|
WAYNE NOTE: COVER Phone #: ###-#### ok final
|
ELE07-02548
| Electrical Rough-In | 8/13/2007 | 8/14/2007 | 8/14/2007 11:14:29 AM | A | PASS |
|
|
WAYNE NOTE: COVER Phone #: ###-#### ok cover ceiling
|
ELE07-00955
| Final | 8/14/2007 | 8/14/2007 | 8/14/2007 10:25:51 AM | A | PASS |
|
|
Access code is 1414 Phone #: ###-#### Internet Inspection Request from: Clyde Logan ok final
|
ELE07-01896
| Electrical Rough-In | 8/13/2007 | 8/14/2007 | 8/14/2007 9:40:45 AM | A | PASS |
|
|
###-#### Internet Inspection Request from: Todd Holbrook ok cover walls & ceilings
|