FIR07-00851
| INSP-Sprinkler Rough-in | 8/14/2008 | 8/14/2008 | 8/15/2008 7:50:40 AM | P | PART |
|
|
Hard lid ceilings at eight rooms as marked on plans with today's date are approved for cover.
|
FIR08-00545
| INSP-Sprinkler Rough-in/Hydro | 8/14/2008 | 8/14/2008 | 8/15/2008 7:48:42 AM | P | FAIL |
|
|
Exposed wood construction above the ceilings at the pendent heads will need coverage as discussed.
|
BLD07-02565
| FIRE-Final Inspection | 8/13/2008 | 8/14/2008 | 8/15/2008 7:46:36 AM | P | PASS |
|
|
Life safety inspection passed.
|
FIR08-00222
| INSP-Sprinkler Rough-in/Hydro | 8/14/2008 | 8/14/2008 | 8/14/2008 2:52:33 PM | P | PART |
|
|
UG fire supply line hydrostatic test passed.
|
FIR08-00355
| INSP-Final Inspection | 8/12/2008 | 8/14/2008 | 8/14/2008 2:51:25 PM | P | PASS |
|
|
Scope of fire alarm work passed field test, permit finaled.
|
FIR08-00417
| INSP-Final Inspection | 8/13/2008 | 8/14/2008 | 8/14/2008 11:15:27 AM | P | NR |
|
|
Project is not ready for final per conversation with general contractor, inspection to be scheduled 8/15.
|
FIR08-00452
| INSP-Final Inspection | 8/13/2008 | 8/14/2008 | 8/14/2008 11:14:04 AM | P | NR |
|
|
Final pending as-built plans for heads relocated in the corridor and tile/escutcheons at all areas.
|
FIR08-00416
| INSP-Final Inspection | 8/13/2008 | 8/14/2008 | 8/14/2008 11:12:38 AM | P | NR |
|
|
Not ready for final at this time due to missing tile and escutcheons per general contractor.
|
FIR08-00503
| INSP-Final Inspection | 8/13/2008 | 8/14/2008 | 8/14/2008 11:08:53 AM | P | FAIL |
|
|
Missing ceiling tile and escutcheons at all sprinkler head locations in the grid ceilings.
|
FIR08-00483
| INSP-Final Inspection | 8/14/2008 | 8/14/2008 | 8/14/2008 10:58:43 AM | P | CANC |
|
|
dave Phone #: ###-#### Inspection cancelled from web by: Alexandra Rahn
|
FIR08-00517
| INSP-Sprinkler Rough-in/Hydro | 8/12/2008 | 8/14/2008 | 8/14/2008 10:35:35 AM | A | PART |
|
|
Inspection for the 4th floor hard lid areas and soffits completed today-okayed for cover at these locations only. Noted blocked upright protection at the NE corner of the reception room-see annotations on approved plan set.
|