Inspections for the day of: Thursday, August 14, 2008.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00851 INSP-Sprinkler Rough-in8/14/20088/14/20088/15/2008 7:50:40 AMPPART
Hard lid ceilings at eight rooms as marked on plans with today's date are approved for cover.
FIR08-00545 INSP-Sprinkler Rough-in/Hydro8/14/20088/14/20088/15/2008 7:48:42 AMPFAIL
Exposed wood construction above the ceilings at the pendent heads will need coverage as discussed.
BLD07-02565 FIRE-Final Inspection8/13/20088/14/20088/15/2008 7:46:36 AMPPASS
Life safety inspection passed.
FIR08-00222 INSP-Sprinkler Rough-in/Hydro8/14/20088/14/20088/14/2008 2:52:33 PMPPART
UG fire supply line hydrostatic test passed.
FIR08-00355 INSP-Final Inspection8/12/20088/14/20088/14/2008 2:51:25 PMPPASS
Scope of fire alarm work passed field test, permit finaled.
FIR08-00417 INSP-Final Inspection8/13/20088/14/20088/14/2008 11:15:27 AMPNR
Project is not ready for final per conversation with general contractor, inspection to be scheduled 8/15.
FIR08-00452 INSP-Final Inspection8/13/20088/14/20088/14/2008 11:14:04 AMPNR
Final pending as-built plans for heads relocated in the corridor and tile/escutcheons at all areas.
FIR08-00416 INSP-Final Inspection8/13/20088/14/20088/14/2008 11:12:38 AMPNR
Not ready for final at this time due to missing tile and escutcheons per general contractor.
FIR08-00503 INSP-Final Inspection8/13/20088/14/20088/14/2008 11:08:53 AMPFAIL
Missing ceiling tile and escutcheons at all sprinkler head locations in the grid ceilings.
FIR08-00483 INSP-Final Inspection8/14/20088/14/20088/14/2008 10:58:43 AMPCANC
dave Phone #: ###-#### Inspection cancelled from web by: Alexandra Rahn
FIR08-00517 INSP-Sprinkler Rough-in/Hydro8/12/20088/14/20088/14/2008 10:35:35 AMAPART
Inspection for the 4th floor hard lid areas and soffits completed today-okayed for cover at these locations only. Noted blocked upright protection at the NE corner of the reception room-see annotations on approved plan set.