FIR09-00033
| INSP-Sprinkler Rough-in | 8/14/2009 | 8/14/2009 | 8/14/2009 5:27:27 PM | P | CANC |
|
|
Overbooked
|
FIR09-00290
| INSP-Final Inspection | 8/14/2009 | 8/14/2009 | 8/14/2009 5:27:09 PM | P | CANC |
|
|
Overbooked
|
BLD07-01784
| FIRE-Final Inspection | 8/12/2009 | 8/14/2009 | 8/14/2009 5:26:18 PM | P | PART |
|
|
Fie life safety walkthrough completed for both buildings, circled items on fire code review notes in need of attention including max. occupant load signs, fire extinguishers-one missing second level, remove manual flush bolt at one pair of doors, need to test EM lighting at some locations with power off, fire sprinkler permit pending corrections, remainder of issues okayed.
|
BLD07-01910
| FIRE-Final Inspection | 8/14/2009 | 8/14/2009 | 8/14/2009 5:18:52 PM | P | PASS |
|
|
Items on correction notice regarding EM lights and exit signs field verified for completion, remainder of building fire life safety inspection passed, discussed permit finals for two outbuildings.
|
FIR08-00045
| INSP-Final Inspection | 8/12/2009 | 8/14/2009 | 8/14/2009 5:15:39 PM | A | FAIL |
|
|
See stamped plan set for locations in need or revision including overspaced heads at the kitchen 103, one overspaced head at the basement hallway, one blocked upright at a closet 1st floor, need to provide access to three locked rooms and the elevator pit, one sw head at the stairway needs the travel cap removed, escutcheons missing at three heads.
|
FIR09-00367
| INSP-Final Inspection | 8/13/2009 | 8/14/2009 | 8/14/2009 2:19:35 PM | A | PASS |
|
|
Fire alarm test for the scope of remodel work completed acceptable, functional testing passed, permit okayed for final. Contractor to provide NFPA 72 record of completion documents for signature at next visit as agreed.
|
FIR09-00246
| INSP-Final Inspection | 8/13/2009 | 8/14/2009 | 8/14/2009 2:16:44 PM | A | PASS |
|
|
Hood suppression system functioned properly under test conditions, contractor to provide "K" class fire extinguisher and post as discussed prior to building final.
|
FIR09-00406
| INSP-Final Inspection | 8/13/2009 | 8/14/2009 | 8/14/2009 1:09:02 PM | A | FAIL |
|
|
Existing manual pull station at the south exit vestibule needs relocated to no higher than 48" AFF to the operable part, location of new notification devices apppears acceptable, will test relocated MP and new a/v's at next site visit.
|
FIR09-00319
| FIR-Aging Inspection | 8/14/2009 | 8/14/2009 | 8/14/2009 1:03:11 PM | | DONE |
|
|
Pending site inspection request for permit final when work is finished.
|
BLD08-02498
| FIRE-Final Inspection | 8/13/2009 | 8/14/2009 | 8/14/2009 1:02:02 PM | A | PASS |
|
|
C/N items verified for completion, fire life safety finaled.
|