Inspections for the day of: Friday, August 14, 2009.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00033 INSP-Sprinkler Rough-in8/14/20098/14/20098/14/2009 5:27:27 PMPCANC
Overbooked
FIR09-00290 INSP-Final Inspection8/14/20098/14/20098/14/2009 5:27:09 PMPCANC
Overbooked
BLD07-01784 FIRE-Final Inspection8/12/20098/14/20098/14/2009 5:26:18 PMPPART
Fie life safety walkthrough completed for both buildings, circled items on fire code review notes in need of attention including max. occupant load signs, fire extinguishers-one missing second level, remove manual flush bolt at one pair of doors, need to test EM lighting at some locations with power off, fire sprinkler permit pending corrections, remainder of issues okayed.
BLD07-01910 FIRE-Final Inspection8/14/20098/14/20098/14/2009 5:18:52 PMPPASS
Items on correction notice regarding EM lights and exit signs field verified for completion, remainder of building fire life safety inspection passed, discussed permit finals for two outbuildings.
FIR08-00045 INSP-Final Inspection8/12/20098/14/20098/14/2009 5:15:39 PMAFAIL
See stamped plan set for locations in need or revision including overspaced heads at the kitchen 103, one overspaced head at the basement hallway, one blocked upright at a closet 1st floor, need to provide access to three locked rooms and the elevator pit, one sw head at the stairway needs the travel cap removed, escutcheons missing at three heads.
FIR09-00367 INSP-Final Inspection8/13/20098/14/20098/14/2009 2:19:35 PMAPASS
Fire alarm test for the scope of remodel work completed acceptable, functional testing passed, permit okayed for final. Contractor to provide NFPA 72 record of completion documents for signature at next visit as agreed.
FIR09-00246 INSP-Final Inspection8/13/20098/14/20098/14/2009 2:16:44 PMAPASS
Hood suppression system functioned properly under test conditions, contractor to provide "K" class fire extinguisher and post as discussed prior to building final.
FIR09-00406 INSP-Final Inspection8/13/20098/14/20098/14/2009 1:09:02 PMAFAIL
Existing manual pull station at the south exit vestibule needs relocated to no higher than 48" AFF to the operable part, location of new notification devices apppears acceptable, will test relocated MP and new a/v's at next site visit.
FIR09-00319 FIR-Aging Inspection8/14/20098/14/20098/14/2009 1:03:11 PM DONE
Pending site inspection request for permit final when work is finished.
BLD08-02498 FIRE-Final Inspection8/13/20098/14/20098/14/2009 1:02:02 PMAPASS
C/N items verified for completion, fire life safety finaled.