FIR12-00401
| INSP-Final Inspection | 8/14/2012 | 8/14/2012 | 8/14/2012 3:50:02 PM | P | PASS |
|
|
Permit finaled
|
BLD11-00317
| FIRE-Conference | 8/14/2012 | 8/14/2012 | 8/14/2012 3:13:20 PM | P | DONE |
|
|
I dicussed the job status with Jeremy with the Boise Fire Dept.
|
FIR12-00429
| INSP-Sprinkler Rough-in/Hydro | 8/13/2012 | 8/14/2012 | 8/14/2012 3:09:36 PM | P | FAIL |
|
|
Showed up at job site but found the underground supply line unable to be installed due to a broken water and gas line.
|
BLD12-00618
| FIRE-Conference | 8/14/2012 | 8/14/2012 | 8/14/2012 2:01:20 PM | P | DONE |
|
|
I discussed the gazebo with Debbie. If it does not meet NFPA 13 for open grid ceiling it will need sprinkler protection installed beneath it.
|
FIR12-00390
| INSP-Final Inspection | 8/13/2012 | 8/14/2012 | 8/14/2012 1:10:37 PM | A | FAIL |
|
|
Need the ceiling tile installed and the new gazebo address per discussion.
|
FIR11-00543
| INSP-Sprinkler Rough-in/Hydro | 8/13/2012 | 8/14/2012 | 8/14/2012 11:48:04 AM | A | PASS |
|
|
Hydro tests of the overhead systems and the remote FDC supply piping passed.
|
BLD12-01188
| FIRE-Final Inspection | 8/13/2012 | 8/14/2012 | 8/14/2012 10:58:07 AM | A | PART |
|
|
A temporary occupancy was given with Scott Arellano's permission until the missing double exit doors/hardware and possible related fire alarm permit has been addressed.
|
BLD12-01454
| FIRE-Final Inspection | 8/13/2012 | 8/14/2012 | 8/14/2012 10:09:21 AM | A | PASS |
|
|
Life safety passed
|
FIR12-00390
| INSP-Sprinkler Rough-in | 8/13/2012 | 8/14/2012 | 8/14/2012 9:53:28 AM | A | PASS |
|
|
Sprinkler piping can be covered.
|
FIR12-00347
| INSP-Final Inspection | 8/13/2012 | 8/14/2012 | 8/14/2012 8:55:53 AM | A | FAIL |
|
|
Underground flush passed. Can't final until the interconnections with the fire alarm system have been verified.
|
FIR12-00330
| INSP-Sprinkler Rough-in/Hydro | 8/13/2012 | 8/14/2012 | 8/14/2012 8:39:26 AM | P | CANC |
|
|
Please call 1/2hr prior to inspection. Dale is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
|
FIR12-00390
| INSP-Final Inspection | 8/13/2012 | 8/14/2012 | 8/13/2012 11:36:06 AM | P | CANC |
|
|
Jeff is contact Phone #: ###-#### >> Inspection requested via web by Connie Danes Inspection cancelled from web by: Connie Danes
|
FIR12-00330
| INSP-Sprinkler Rough-in/Hydro | 8/13/2012 | 8/14/2012 | 8/13/2012 9:56:05 AM | A | CANC |
|
|
Please call 1/2 hr prior to inspection. Dale is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
|