Inspections for the day of: Thursday, August 14, 2014.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD14-00729 FIRE-Final Inspection8/14/20148/14/20148/14/2014 5:00:04 PMPFAIL
Need to adjust door closures at the second floor units, project related fire alarm and sprinkler permit finals pending repairs and adjustments.
FIR14-00336 INSP-Final Inspection8/12/20148/14/20148/14/2014 4:58:02 PMPPART
Final pending flow switch repair. Remainder of fire alarm work tested satisfactory.
FIR14-00384 INSP-Final Inspection8/13/20148/14/20148/14/2014 4:55:04 PMPPART
Items needed prio to final include; repair flow switch at the riser, install missing escutcheons, remove tape at one DSW.
FIR14-00474 INSP-Sprinkler Rough-in/Hydro8/14/20148/14/20148/14/2014 4:51:59 PMPPART
UG fire supply line passed hydrostatic testing within allowable leakage per NFPA 13.
FIR14-00502 INSP-Sprinkler Rough-in8/14/20148/14/20148/14/2014 4:50:57 PMPPART
Overhead fire sprinkler modifications okayed for cover at the drop ceilings.
BLD13-02102 FIRE-Final Inspection8/14/20148/14/20148/14/2014 4:49:02 PMPPASS
Verified plan resubmittals and previous correction items. Life safety final approved.
FIR13-00723 INSP-Sprinkler Rough-in/Hydro8/14/20148/14/20148/14/2014 4:44:02 PMPPART
OH hydrostatic testing completed acceptable.
BLD13-01281 FIRE-Final Inspection8/14/20148/14/20148/14/2014 4:39:46 PMPPASS
C/N items field verified. Life safety finaled.
BLD14-01977 FIRE-Final Inspection8/13/20148/14/20148/14/2014 12:01:10 PMAPASS
Fire life safety inspection completed satisfactory.
FIR14-00564 INSP-Sprinkler Rough-in8/13/20148/14/20148/14/2014 11:06:12 AMAPART
Okay to cover overhead fire sprinkler work at the new restroom sheetrock ceiling.
FIR14-00561 INSP-Final Inspection8/13/20148/14/20148/14/2014 10:23:02 AMAPASS
Scope of fire alarm work passed inspection and testing. Permit finaled.
BLD14-00245 FIRE-Final Inspection8/13/20148/14/20148/14/2014 9:04:51 AMAPASS
Life safety inspection passed.