BLD17-01278
| FIRE-Final Inspection | 8/14/2017 | 8/14/2017 | 8/14/2017 2:50:12 PM | P | PASS |
|
|
Fire sprinkler inspection complete, fire alarm inspection complete (Mag locks for tenant space release on general fire alarm), fire extinguishers are in place with current inspection tags. Final life fire safety inspection for area of work passed/complete.
|
FIR17-00426
| INSP-Final Inspection | 8/14/2017 | 8/14/2017 | 8/14/2017 2:48:46 PM | P | PASS |
|
|
Previously noted items have been addressed/repaired. Final fire alarm inspection for area of work passed/complete.
|
NAF17-00041
| INSP-Sprinkler Rough-in/Hydro | 8/14/2017 | 8/14/2017 | 8/14/2017 2:05:44 PM | P | PART |
|
|
Hydrostatic test complete for both wet and dry systems in area of work. Rough to cover inspection for dry systen complete, dry system is approved for cover. Rough in inspection complete for wet system area of work, wet system piping cannot be covered until tenting of wet system overhead fire sprinkler piping is complete and inspected.
|
FIR17-00217
| INSP-Sprinkler Rough-in | 8/11/2017 | 8/14/2017 | 8/14/2017 1:51:04 PM | P | FAIL |
|
|
Tenting not complete on levels 3 and 4. Inspection stopped after finding numerous hangers overspaced on levels 3 and 4.
|
FIR17-00217
| INSP-Sprinkler Rough-in/Hydro | 8/11/2017 | 8/14/2017 | 8/14/2017 1:49:37 PM | P | PART |
|
|
Htdrostatic test complete for levels 2, 3 and 4. Level 1 to be completed at a later date.
|
NAF17-00050
| INSP-Final | 8/11/2017 | 8/14/2017 | 8/14/2017 11:37:24 AM | A | DONE |
|
|
Previously noted items have been repaired, final fire alarm inspection for area of work passed/complete.
|
FIR17-00211
| INSP-Final Inspection | 8/11/2017 | 8/14/2017 | 8/14/2017 9:04:39 AM | A | PASS |
|
|
Final fire alarm inspection for area of work passed/complete.
|
FIR16-00357
| INSP-Final Inspection | 8/11/2017 | 8/14/2017 | 8/14/2017 9:04:12 AM | A | PASS |
|
|
Previously noted items have been repaired, final fire alarm inspection for area of work passed/complete.
|
FIR17-00217
| INSP-Sprinkler Rough-in/Hydro | 8/11/2017 | 8/14/2017 | 8/11/2017 11:13:41 AM | A | CANC |
|
|
Call Jake before heading out, thanks! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
|