ELE15-00291
| ELE-Aging Inspection | 8/14/2019 | 8/14/2019 | 8/15/2019 10:45:44 AM | | DONE |
|
|
Still waiting
|
ELE18-04053
| Electrical Rough-In | 8/14/2019 | 8/14/2019 | 8/14/2019 2:43:48 PM | P | PASS |
|
|
Contact: Mike Mulvahill.... fire pump inspection please Phone #: ###-#### Inspection requested via web by Deb Gooden Fire pump ok
|
ELE19-02829
| Permanent Service | 8/14/2019 | 8/14/2019 | 8/14/2019 2:43:06 PM | P | PASS |
|
|
Contact: Mike Mulvahill Phone #: ###-#### Inspection requested via web by Deb Gooden AFC 9181 p/s u/g n ok
|
ELE19-03031
| Conference | 8/14/2019 | 8/14/2019 | 8/14/2019 1:58:30 PM | P | DONE |
|
|
Any time after noon is preferable, thanks. Phone #: ###-#### Inspection requested via web by Angelo Neglia Discussed wiring of basement and code realated items. Ceiling will remain open, owner has a good handle on job that is needed and is electrical designe/engineer and is capable of this work...
|
ELE19-03031
| Conference | 8/14/2019 | 8/14/2019 | 8/14/2019 1:57:10 PM | P | CANC |
|
|
Any time after noon is preferable, thanks. Phone #: ###-#### Inspection requested via web by Angelo Neglia Duplicate request
|
ELE19-03036
| Conference | 8/14/2019 | 8/14/2019 | 8/14/2019 1:10:26 PM | P | DONE |
|
|
Ron Phone #: ###-####-please call 20 minutes prior to meet for access Discussed code requirements for bathroom being added downstairs
|
ELE19-03036
| Electrical Rough-In | 8/14/2019 | 8/14/2019 | 8/14/2019 1:09:49 PM | P | CANC |
|
|
Ron Phone #: ###-####please call 20 minutes prior to meet for access
|
ELE19-03037
| Electrical Rough-In | 8/14/2019 | 8/14/2019 | 8/14/2019 12:38:36 PM | P | CANC |
|
|
Phone #: ###-#### Inspection requested via web by Deb Ipsen Needed Final
|
ELE19-03037
| Final | 8/14/2019 | 8/14/2019 | 8/14/2019 12:38:08 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Deb Ipsen Final ok for sign circuit
|
ELE19-01233
| Permanent Service | 8/14/2019 | 8/14/2019 | 8/14/2019 11:29:02 AM | A | FAIL |
|
|
Contractor will not be on site. This is a new service for t mobile cell site. Gate combo is 7011. Please call Bryan with any questions ###-#### Phone #: ###-#### Inspection requested via web by Bryan Howard 110.25 AFC calc required for service proir to energize
|
ELE19-02827
| Final | 8/14/2019 | 8/14/2019 | 8/14/2019 11:23:41 AM | P | PASS |
|
|
Verified with contractor rough-in specifications on solar install and scope of work. All components all U/L listed will final out permit as needed Final ok
|
ELE19-02827
| Final | 8/13/2019 | 8/14/2019 | 8/14/2019 11:01:38 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Seth Stears Final ok
|
ELE19-01285
| Final | 8/13/2019 | 8/14/2019 | 8/14/2019 10:21:28 AM | A | PASS |
|
|
Lock box to get is is 2730. Thanks Phone #: ###-#### Inspection requested via web by Dylan Pierce Final ok
|
ELE19-01595
| Final | 8/8/2019 | 8/14/2019 | 8/14/2019 9:37:55 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Craig Korell Reverse polarity on counter receptacles 406 Tamper resistant on all GFCI receptacles 210.8 GFCI All receptacles located within 6' of sink shall have GFCI protection(accross from sink) 110.25 Lockable means of lockout required for hard wired appliances(hood)
|
ELE15-01149
| ELE-Aging Inspection | 8/14/2019 | 8/14/2019 | 8/14/2019 8:32:06 AM | | FAIL |
|
|
Still waiting
|