Inspections for the day of: Wednesday, August 14, 2019.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorEric Story
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE15-00291 ELE-Aging Inspection8/14/20198/14/20198/15/2019 10:45:44 AM DONE
Still waiting
ELE18-04053 Electrical Rough-In8/14/20198/14/20198/14/2019 2:43:48 PMPPASS
Contact: Mike Mulvahill.... fire pump inspection please Phone #: ###-#### Inspection requested via web by Deb Gooden
Fire pump ok
ELE19-02829 Permanent Service8/14/20198/14/20198/14/2019 2:43:06 PMPPASS
Contact: Mike Mulvahill Phone #: ###-#### Inspection requested via web by Deb Gooden
AFC 9181
p/s u/g n ok
ELE19-03031 Conference8/14/20198/14/20198/14/2019 1:58:30 PMPDONE
Any time after noon is preferable, thanks. Phone #: ###-#### Inspection requested via web by Angelo Neglia
Discussed wiring of basement and code realated items. Ceiling will remain open, owner has a good handle on job that is needed and is electrical designe/engineer and is capable of this work...
ELE19-03031 Conference8/14/20198/14/20198/14/2019 1:57:10 PMPCANC
Any time after noon is preferable, thanks. Phone #: ###-#### Inspection requested via web by Angelo Neglia
Duplicate request
ELE19-03036 Conference8/14/20198/14/20198/14/2019 1:10:26 PMPDONE
Ron Phone #: ###-####-please call 20 minutes prior to meet for access
Discussed code requirements for bathroom being added downstairs
ELE19-03036 Electrical Rough-In8/14/20198/14/20198/14/2019 1:09:49 PMPCANC
Ron Phone #: ###-####please call 20 minutes prior to meet for access
ELE19-03037 Electrical Rough-In8/14/20198/14/20198/14/2019 12:38:36 PMPCANC
Phone #: ###-#### Inspection requested via web by Deb Ipsen
Needed Final
ELE19-03037 Final8/14/20198/14/20198/14/2019 12:38:08 PMPPASS
Phone #: ###-#### Inspection requested via web by Deb Ipsen
Final ok for sign circuit
ELE19-01233 Permanent Service8/14/20198/14/20198/14/2019 11:29:02 AMAFAIL
Contractor will not be on site. This is a new service for t mobile cell site. Gate combo is 7011. Please call Bryan with any questions ###-#### Phone #: ###-#### Inspection requested via web by Bryan Howard
110.25 AFC calc required for service proir to energize
ELE19-02827 Final8/14/20198/14/20198/14/2019 11:23:41 AMPPASS
Verified with contractor rough-in specifications on solar install and scope of work.
All components all U/L listed will final out permit as needed
Final ok
ELE19-02827 Final8/13/20198/14/20198/14/2019 11:01:38 AMAPASS
Phone #: ###-#### Inspection requested via web by Seth Stears
Final ok
ELE19-01285 Final8/13/20198/14/20198/14/2019 10:21:28 AMAPASS
Lock box to get is is 2730. Thanks Phone #: ###-#### Inspection requested via web by Dylan Pierce
Final ok
ELE19-01595 Final8/8/20198/14/20198/14/2019 9:37:55 AMAFAIL
Phone #: ###-#### Inspection requested via web by Craig Korell
Reverse polarity on counter receptacles
406 Tamper resistant on all GFCI receptacles
210.8 GFCI All receptacles located within 6' of sink shall have GFCI protection(accross from sink)
110.25 Lockable means of lockout required for hard wired appliances(hood)
ELE15-01149 ELE-Aging Inspection8/14/20198/14/20198/14/2019 8:32:06 AM FAIL
Still waiting