FIR01-00126
| INSP-Sprinkler Rough-in/Hydro | 8/14/2003 | 8/15/2003 | 8/15/2003 12:00:00 AM | A | FAIL |
|
|
Trip tests, and alarm test on the fire sprinkler system. Please call in the A.M. so we can have things ready when you arrive.; Phone #: ###-#### Internet Inspection Request from: Trent Bice need head under overhead door and return bends; remove main; need sign on door - Fire Sprinkler Controls - Fire Alarm Panel; keep hose valves clear of storage; obtain approval for 62 second trip time; provide locks on EOL acclerator; lock on PIV; PIV tamper undergorund conduit not listed for underground service; 8/15/2003 11:48:10 AM
|
FIR01-00152
| INSP-Final Inspection | 8/15/2003 | 8/15/2003 | 8/15/2003 12:00:00 AM | A | FAIL |
|
|
need approved plans; 12 amp hr batteries; horn not installed; zones not per plans; need verification/listing of the blue flex conduit for use in underground for PIV tamper; NFPA 72 Record of Completion; zones not defined; need to verify 2nd phone line trouble; need proper smoke detector per plans; need circuit breaker location and lockout 8/15/2003 11:45:18 AM
|
BLD03-01117
| FIRE-Final Inspection | 8/15/2003 | 8/15/2003 | 8/15/2003 12:00:00 AM | P | PASS |
|
|
|
FIR02-00477
| INSP-Sprinkler Rough-in/Hydro | 8/14/2003 | 8/15/2003 | 8/15/2003 12:00:00 AM | P | PART |
|
|
Call prior to arrival so that we can have system charged. Foremans name is Rudi.; Phone #: ###-#### Internet Inspection Request from: Trent Bice hydro on perimeter racking okay 8/15/2003 3:41:20 PM
|
FIR03-00300
| INSP-Final Inspection | 8/15/2003 | 8/15/2003 | 8/15/2003 12:00:00 AM | P | PART |
|
|
Scheduled by a contractor via Hello! on 8/15/2003 at 7:41:42 AM. Contact: ###-####. okay to cover but will need to verify room type occupancies (light/OH-1) at final 8/15/2003 3:32:26 PM
|
BLD03-00713
| FIRE-Final Inspection | 8/15/2003 | 8/15/2003 | 8/15/2003 12:00:00 AM | P | PASS |
|
|
###-#### larry
|
FIR03-00420
| INSP-Final Inspection | 8/15/2003 | 8/15/2003 | 8/15/2003 12:00:00 AM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Terry Owsley
|
FIR03-00152
| INSP-Sprinkler Rough-in/Hydro | 8/15/2003 | 8/15/2003 | 8/15/2003 12:00:00 AM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 8/15/2003 at 10:07:03 AM. Contact: ###-####. hydro on wet system dropped 4 psi 8/15/2003 2:28:31 PM
|