Inspections for the day of: Tuesday, August 15, 2006.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-01340 Final8/15/20068/15/20068/15/2006 3:44:54 PMPPASS
justin; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley
ELE06-03008 Electrical Rough-In8/14/20068/15/20068/15/2006 3:04:46 PMPFAIL
dan ###-#### corr. fee due called 314.16 box fill
master bath, 250.122 use #12 for 20 amp equip grd pigtails, 300.4 nail plates and 11/4", 210.52(A) outlet spacing N W corner exercise rm, 314.17 (A&C) replace 2 gang boxes with broken clamps, 334,23 protect cables within 6 ft of attic access, note complete all wiring install all recess fixtures, update permit from 2rms to 11rms
ELE06-02605 Electrical Rough-In8/15/20068/15/20068/15/2006 2:20:25 PMPPART
butch - underground homeside concession stand area (30' ditch); Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok west side
ELE06-01487 Final8/15/20068/15/20068/15/2006 1:44:42 PMPPASS
garage access 781 enter Internet Inspection Request from: Melyne Davis
ELE06-01338 Final8/15/20068/15/20068/15/2006 1:44:26 PMPPASS
garage access code 791 enter Internet Inspection Request from: Melyne Davis
ELE06-00571 Final8/15/20068/15/20068/15/2006 1:16:22 PMPPASS
Internet Inspection Request from: Melyne Davis ok
ELE06-00634 Final8/11/20068/15/20068/15/2006 12:43:06 PMAFAIL
TOM; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called no response never had r/i for walls, only ceiling
ELE05-02003 Electrical Rough-In8/14/20068/15/20068/15/2006 11:46:42 AMAPART
jerod Note; exercise room 1st floor; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok anop
ELE05-03660 Final8/14/20068/15/20068/15/2006 10:26:29 AMANR
need a final on what is completed so they can get occupancy, Call Anita ###-#### to get access to building. Any questions call George @ ###-#### Internet Inspection Request from: Andy Rose called install outlet west end parking lot, needs conn for mc range hoods, bond hot and cold, box extensions, paneling, no splices allowed in zip cord chain suppended fixtures
ELE06-02975 Electrical Rough-In8/14/20068/15/20068/15/2006 9:28:37 AMAPART
Inspection for ceiling in main walk thru area so owner can install insulation and drywall.; Phone #: ###-#### Internet Inspection Request from: todd hall ok
ELE06-03010 Final8/14/20068/15/20068/15/2006 8:49:04 AMANH
david ###-#### called no access

ELE06-01470 Electrical Rough-In8/14/20068/15/20068/15/2006 8:15:12 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Barbara Stitt ok