FIR06-00045
| INSP-Final Inspection | 8/15/2006 | 8/15/2006 | 8/21/2006 10:25:49 AM | P | CANC |
|
|
curt; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley No contact due to incorrect phone number
|
FIR05-00883
| INSP-Sprinkler Rough-in/Hydro | 8/14/2006 | 8/15/2006 | 8/16/2006 9:34:33 AM | P | CANC |
|
|
Wrong permit number requested for inspection.
|
FIR06-00541
| INSP-Alarm Testing | 8/14/2006 | 8/15/2006 | 8/15/2006 4:53:55 PM | P | FAIL |
|
|
Three duct detectors are incorrectly installed, wall mounted av in the electrical room appears to be a ceiling only av, partial test only of the 2nd floor completed today.
|
FIR06-00418
| INSP-Sprinkler Rough-in/Hydro | 8/14/2006 | 8/15/2006 | 8/15/2006 4:41:31 PM | P | PART |
|
|
OH rough-in at the drop ceiling areas is okay to cover, the telephone room will require a drop ceiling and pendent sprinkler or walls must extend to the deck for upright protection.
|
BLD04-02464
| FIRE-Sprinkler Rough-in | 8/15/2006 | 8/15/2006 | 8/15/2006 3:26:39 PM | P | PART |
|
|
Inspection for approval to cover OH fire sprinkler installation at the Dollar store drop ceiling areas, rough-in is okay for the drop ceiling only. Noted to GC the fire sprinkler permit is only issued in a "partial" status due to resubmittal items required per plan review. Also noted that it appears no UG permit for the fire supply connection has been issued for bldg A1.
|
FIR06-00348
| INSP-Sprinkler Rough-in/Hydro | 8/14/2006 | 8/15/2006 | 8/15/2006 2:59:29 PM | P | PART |
|
|
Hydrostatic test of the dry system installation passed, rough-in inspection not completed at this time.
|
FIR05-00901
| INSP-Sprinkler Rough-in/Hydro | 8/14/2006 | 8/15/2006 | 8/15/2006 1:14:48 PM | P | DEFR |
|
|
No time to complete inspection today, not all floors are ready for hydro per phone call from contractor, to be rescheduled.
|
FIR06-00092
| INSP-Final Inspection | 8/15/2006 | 8/15/2006 | 8/15/2006 12:55:40 PM | P | DEFR |
|
|
No time to complete inspection, to be rescheduled per conversation with contractor.
|
FIR06-00457
| INSP-Final Inspection | 8/9/2006 | 8/15/2006 | 8/15/2006 12:53:05 PM | A | FAIL |
|
|
SD is not properly located in the ceiling with regard to the minimum distance away from an adjacent HVAC diffuser.
|
BLD05-01077
| FIRE-Sprinkler Rough-in | 8/15/2006 | 8/15/2006 | 8/15/2006 12:03:14 PM | P | PART |
|
|
Inspection requested for sprinkler cover at the guest rooms adjacent to the temp. elevator at the 10th floor is okay, the 11th floor guest room at this location is not ready for inspection.
|
MIS06-00203
| FIR-Final | 8/14/2006 | 8/15/2006 | 8/15/2006 12:00:02 PM | P | PASS |
|
|
Life safety is acceptable pending change out of locking door hardware at the break room to be completed prior to structural final.
|
FIR06-00421
| INSP-Sprinkler Rough-in | 8/15/2006 | 8/15/2006 | 8/15/2006 10:48:55 AM | A | DONE |
|
|
Duplicate inspection request.
|
FIR05-00698
| FIR-Aging Inspection | 8/15/2006 | 8/15/2006 | 8/15/2006 10:42:37 AM | | DONE |
|
|
wip
|
FIR06-00421
| INSP-Sprinkler Rough-in | 8/15/2006 | 8/15/2006 | 8/15/2006 10:42:10 AM | A | PART |
|
|
The remainder of OH rough-in at the hard lid areas is good for cover.
|
FIR06-00508
| INSP-Final Inspection | 8/14/2006 | 8/15/2006 | 8/15/2006 10:30:40 AM | A | FAIL |
|
|
Need to provide missing hangers at three new arm-overs in the warehouse area, noted the existing riser is not monitored and the dry system main control is shut, ceiling tile adjacent to sprinkler heads in the office area must be reinstalled prior to final.
|
FIR06-00467
| INSP-Final Inspection | 8/14/2006 | 8/15/2006 | 8/15/2006 9:54:17 AM | A | PASS |
|
|
Fire sprinkler installation is acceptable, contractor still needs to provide spare heads of the type installed in the head box at the riser.
|