Inspections for the day of: Tuesday, August 15, 2006.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00045 INSP-Final Inspection8/15/20068/15/20068/21/2006 10:25:49 AMPCANC
curt; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley No contact due to incorrect phone number
FIR05-00883 INSP-Sprinkler Rough-in/Hydro8/14/20068/15/20068/16/2006 9:34:33 AMPCANC
Wrong permit number requested for inspection.
FIR06-00541 INSP-Alarm Testing8/14/20068/15/20068/15/2006 4:53:55 PMPFAIL
Three duct detectors are incorrectly installed, wall mounted av in the electrical room appears to be a ceiling only av, partial test only of the 2nd floor completed today.
FIR06-00418 INSP-Sprinkler Rough-in/Hydro8/14/20068/15/20068/15/2006 4:41:31 PMPPART
OH rough-in at the drop ceiling areas is okay to cover, the telephone room will require a drop ceiling and pendent sprinkler or walls must extend to the deck for upright protection.
BLD04-02464 FIRE-Sprinkler Rough-in8/15/20068/15/20068/15/2006 3:26:39 PMPPART
Inspection for approval to cover OH fire sprinkler installation at the Dollar store drop ceiling areas, rough-in is okay for the drop ceiling only. Noted to GC the fire sprinkler permit is only issued in a "partial" status due to resubmittal items required per plan review. Also noted that it appears no UG permit for the fire supply connection has been issued for bldg A1.
FIR06-00348 INSP-Sprinkler Rough-in/Hydro8/14/20068/15/20068/15/2006 2:59:29 PMPPART
Hydrostatic test of the dry system installation passed, rough-in inspection not completed at this time.
FIR05-00901 INSP-Sprinkler Rough-in/Hydro8/14/20068/15/20068/15/2006 1:14:48 PMPDEFR
No time to complete inspection today, not all floors are ready for hydro per phone call from contractor, to be rescheduled.
FIR06-00092 INSP-Final Inspection8/15/20068/15/20068/15/2006 12:55:40 PMPDEFR
No time to complete inspection, to be rescheduled per conversation with contractor.
FIR06-00457 INSP-Final Inspection8/9/20068/15/20068/15/2006 12:53:05 PMAFAIL
SD is not properly located in the ceiling with regard to the minimum distance away from an adjacent HVAC diffuser.
BLD05-01077 FIRE-Sprinkler Rough-in8/15/20068/15/20068/15/2006 12:03:14 PMPPART
Inspection requested for sprinkler cover at the guest rooms adjacent to the temp. elevator at the 10th floor is okay, the 11th floor guest room at this location is not ready for inspection.
MIS06-00203 FIR-Final8/14/20068/15/20068/15/2006 12:00:02 PMPPASS
Life safety is acceptable pending change out of locking door hardware at the break room to be completed prior to structural final.
FIR06-00421 INSP-Sprinkler Rough-in8/15/20068/15/20068/15/2006 10:48:55 AMADONE
Duplicate inspection request.
FIR05-00698 FIR-Aging Inspection8/15/20068/15/20068/15/2006 10:42:37 AM DONE
wip
FIR06-00421 INSP-Sprinkler Rough-in8/15/20068/15/20068/15/2006 10:42:10 AMAPART
The remainder of OH rough-in at the hard lid areas is good for cover.
FIR06-00508 INSP-Final Inspection8/14/20068/15/20068/15/2006 10:30:40 AMAFAIL
Need to provide missing hangers at three new arm-overs in the warehouse area, noted the existing riser is not monitored and the dry system main control is shut, ceiling tile adjacent to sprinkler heads in the office area must be reinstalled prior to final.
FIR06-00467 INSP-Final Inspection8/14/20068/15/20068/15/2006 9:54:17 AMAPASS
Fire sprinkler installation is acceptable, contractor still needs to provide spare heads of the type installed in the head box at the riser.