Inspections for the day of: Tuesday, August 15, 2006.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD06-01174 FIRE-Final Inspection8/15/20068/15/20068/15/2006 4:47:44 PMPFAIL
Testing today was for the exit signs/emergency lights for all areas north of the mountain. All devices worked except for an emergency light at the exit from the warehouse to the gun sales and the exit light from the gun library has no battery backup.
BLD06-01824 FIRE-Final Inspection8/15/20068/15/20068/15/2006 4:45:03 PMPFAIL
Provide signage as discussed to limit the storage height at the racks to 20'-0".
FIR05-00586 INSP-Final Inspection8/15/20068/15/20068/15/2006 3:41:43 PMPPASS
Permit finaled
FIR06-00463 INSP-Sprinkler Rough-in8/14/20068/15/20068/15/2006 3:25:48 PMPPASS
Sprinkler rough-in passed. Additional coverage is required under the intermediate landing in both stairwells. Riser items not completed yet.
FIR06-00544 INSP-Final Inspection8/14/20068/15/20068/15/2006 2:29:35 PMPFAIL
This inspection was for phase 1 only. The sprinkler piping in phase 1 is ok to cover.
BLD06-01617 FIRE-Final Inspection8/15/20068/15/20068/15/2006 1:53:23 PMPPASS
life safety finaled.
FIR06-00465 INSP-Final Inspection8/15/20068/15/20068/15/2006 1:43:48 PMPPASS
Permit finaled
FIR06-00419 INSP-Alarm Testing8/14/20068/15/20068/15/2006 11:50:19 AMADONE
Sound test passed today for the audio/visual devices. Four problems that need addressed are the strobe in the northeast service corridor is overspaced, the sound level in the storage room adjacent to the archery ranch is too low and both ceiling mount a/v's in the fly shop are not at the correct candella. All sprinkler items need addressed and the two horns in the fish tank/mechanical room need installed.
FIR06-00398 INSP-Final Inspection8/14/20068/15/20068/15/2006 10:24:58 AMAPASS
24 hour air test on both dry systems passed.