BLD06-01174
| FIRE-Final Inspection | 8/15/2006 | 8/15/2006 | 8/15/2006 4:47:44 PM | P | FAIL |
|
|
Testing today was for the exit signs/emergency lights for all areas north of the mountain. All devices worked except for an emergency light at the exit from the warehouse to the gun sales and the exit light from the gun library has no battery backup.
|
BLD06-01824
| FIRE-Final Inspection | 8/15/2006 | 8/15/2006 | 8/15/2006 4:45:03 PM | P | FAIL |
|
|
Provide signage as discussed to limit the storage height at the racks to 20'-0".
|
FIR05-00586
| INSP-Final Inspection | 8/15/2006 | 8/15/2006 | 8/15/2006 3:41:43 PM | P | PASS |
|
|
Permit finaled
|
FIR06-00463
| INSP-Sprinkler Rough-in | 8/14/2006 | 8/15/2006 | 8/15/2006 3:25:48 PM | P | PASS |
|
|
Sprinkler rough-in passed. Additional coverage is required under the intermediate landing in both stairwells. Riser items not completed yet.
|
FIR06-00544
| INSP-Final Inspection | 8/14/2006 | 8/15/2006 | 8/15/2006 2:29:35 PM | P | FAIL |
|
|
This inspection was for phase 1 only. The sprinkler piping in phase 1 is ok to cover.
|
BLD06-01617
| FIRE-Final Inspection | 8/15/2006 | 8/15/2006 | 8/15/2006 1:53:23 PM | P | PASS |
|
|
life safety finaled.
|
FIR06-00465
| INSP-Final Inspection | 8/15/2006 | 8/15/2006 | 8/15/2006 1:43:48 PM | P | PASS |
|
|
Permit finaled
|
FIR06-00419
| INSP-Alarm Testing | 8/14/2006 | 8/15/2006 | 8/15/2006 11:50:19 AM | A | DONE |
|
|
Sound test passed today for the audio/visual devices. Four problems that need addressed are the strobe in the northeast service corridor is overspaced, the sound level in the storage room adjacent to the archery ranch is too low and both ceiling mount a/v's in the fly shop are not at the correct candella. All sprinkler items need addressed and the two horns in the fish tank/mechanical room need installed.
|
FIR06-00398
| INSP-Final Inspection | 8/14/2006 | 8/15/2006 | 8/15/2006 10:24:58 AM | A | PASS |
|
|
24 hour air test on both dry systems passed.
|