Inspections for the day of: Wednesday, August 15, 2007.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-02712 Permanent Service8/15/20078/15/20078/15/2007 4:19:39 PMPCANC
Ufer Ground Only. Phone #: ###-#### Internet Inspection Request from: Dan Rohl see ri
ELE07-02712 Electrical Rough-In8/15/20078/15/20078/15/2007 4:06:04 PMPPASS
Ufer Ground Only. Phone #: ###-#### Internet Inspection Request from: Dan Rohl ok to cover gec with backfill
ELE07-02351 Final8/15/20078/15/20078/15/2007 3:50:04 PMPPASS
Carol; Phone #: ###-#### Internet Inspection Request from: Hattie James corrections made, ok to final
ELE07-02524 Electrical Rough-In8/15/20078/15/20078/15/2007 3:29:54 PMPPART
wayne Note: trench Phone #: ###-#### ok to cover east street side and north street side for lot lights only
ELE07-01392 Final8/15/20078/15/20078/15/2007 2:48:11 PMPPASS
Roger, please call 1st for access; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ok to final
ELE07-01489 Final8/15/20078/15/20078/15/2007 2:25:46 PMPPASS
Roger, please call 1st for access; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ok to final
ELE07-01566 Final8/15/20078/15/20078/15/2007 2:00:03 PMPPASS
Roger, please call 1st for access; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt called contr to set a/c, ok to final
ELE07-02506 Electrical Rough-In8/15/20078/15/20078/15/2007 1:23:14 PMPPASS
We need a ceiling cover inspection
thanks Phone #: ###-#### Internet Inspection Request from: Scott Abbott met elect, ceiling only ok to cover, will call for final ltr
ELE07-01551 Electrical Rough-In8/14/20078/15/20078/15/2007 12:44:56 PMPPART
Joe; second floor rooms; Phone #: ###-#### Internet Inspection Request from: Hattie James 2nd floor rooms only ok to final anop
ELE07-00599 Permanent Service8/14/20078/15/20078/15/2007 11:49:28 AMAPASS
Scheduled by a contractor via Hello! on 8/14/2007 at 12:47:22 PM. Contact: ###-####. p/s u/g rec ok
ELE07-02839 Temporary Service8/14/20078/15/20078/15/2007 9:52:18 AMAPASS
Andy; Phone #: ###-#### Internet Inspection Request from: Hattie James t/s o/h n ok
ELE07-02246 Electrical Rough-In8/14/20078/15/20078/15/2007 9:36:28 AMAPASS
Scheduled by a contractor via Hello! on 8/14/2007 at 10:30:25 AM. Contact: ###-####. walls and ceiling ok to cover
ELE07-01153 Electrical Rough-In8/14/20078/15/20078/15/2007 9:15:21 AMAPART
Scheduled by a contractor via Hello! on 8/14/2007 at 10:28:59 AM. Contact: ###-####. ceiling only ok to cover
ELE07-00609 Final8/14/20078/15/20078/15/2007 8:47:23 AMAFAIL
The back left building is ready for final inspection please call Brad with any questions thank you Phone #: ###-#### Internet Inspection Request from: Brad Baker called, left corr notice,,nec 406.4 hall recpt shall be securely mounted, 422.31(B) shall provide furnace disconnects, 110.22 disconnects shall be legibly marked (furnace), 110.3(B) listed equipment shall be installed per mfgrs instructions (break room recpts shall operate), BCC all u/g shall be seen before cover (outside light), shall provide correct bld and elec permits (no occ card), shall provide permanent address, Note: no access to rear of bldg-shall inspect later for possible corrections
ELE07-02342 Electrical Rough-In8/14/20078/15/20078/15/2007 8:36:58 AMAPASS
rough in for walls Phone #: ###-#### Internet Inspection Request from: Tracy Robertson corr made, ric walls only ok
ELE07-02499 Electrical Rough-In8/15/20078/15/20078/15/2007 12:00:00 AMPCANC
sam Phone #: ###-####