Inspections for the day of: Wednesday, August 15, 2007.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD07-01341 FIRE-Final Inspection8/14/20078/15/20078/23/2007 1:57:36 PMAFAIL
Need to provide approved hardware at the doors to the mens and womens restrooms.
BLD07-01349 FIRE-Final Inspection8/14/20078/15/20078/17/2007 2:08:55 PMAFAIL
Hardware is not approved at the restroom doors.
FIR07-00474 INSP-Final Inspection8/14/20078/15/20078/15/2007 4:36:06 PMANR
Project is not ready for final inspection at this time.
FIR07-00462 INSP-Final Inspection8/15/20078/15/20078/15/2007 4:31:20 PMPNR
Pending project related fire sprinkler work completion.
BLD07-00352 FIRE-Final Inspection8/15/20078/15/20078/15/2007 4:29:38 PMPPASS
Fire life safety finaled.
FIR07-00656 INSP-Final Inspection8/15/20078/15/20078/15/2007 4:28:53 PMPPASS
Final fire sprinkler inspection passed, permit finaled.
FIR07-00593 INSP-Sprinkler Rough-in/Hydro8/15/20078/15/20078/15/2007 3:23:55 PMPFAIL
Two heads on the second floor are obstructed by ceilng mounted beams, noted three areas lacking sufficient cold cavity protection, one SW head adjusted while on site.
BLD07-00919 FIRE-Final Inspection8/15/20078/15/20078/15/2007 3:21:46 PMPFAIL
Noted modifications to the existing fire alarm system have been made per site visit and as indicated on approved plans sheet E2.1. Any alteration, extension or modification to an existing FA system requires a fire alarm permit and field inspection for code compliance. This will need to be completed prior to a BLD life safety final.
FIR07-00316 INSP-Supply line flush8/15/20078/15/20078/15/2007 1:39:49 PMPPART
UG fire supply line flush completed satisfactory.
FIR07-00568 INSP-Supply line flush8/14/20078/15/20078/15/2007 11:16:44 AMACANC
Wrong permit number called in for inspection.
FIR07-00624 INSP-Final Inspection8/14/20078/15/20078/15/2007 10:40:59 AMAFAIL
Two heads at the waiting area exceed min. spacing allowed, need to provide verification that the existing system design will support more than one head piped off a single 1" outlet (noted 4 heads are supplied off one 1" outlet at the lobby) or install heads as shown on approved plan.