Inspections for the day of: Friday, August 15, 2008.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE08-02230 Conference8/15/20088/15/20088/15/2008 2:54:22 PMPDONE
Linda Phone #: ###-#### ok
ELE08-02302 Permanent Service8/15/20088/15/20088/15/2008 2:09:22 PMPFAIL
jason Phone #: ###-#### 250.94 needs bus for other services, remove phone and tv conduits from below p/s and shall nor splice GEC also needs connector for it called
ELE07-01689 Permanent Service8/15/20088/15/20088/15/2008 1:27:17 PMPPASS
Troy Phone #: ###-#### p/s o/h rec. ok
ELE07-01689 Conference8/15/20088/15/20088/15/2008 1:27:06 PMPDONE
Troy Phone #: ###-#### 01 about service to detached garage
ELE08-02281 Electrical Rough-In8/15/20088/15/20088/15/2008 12:26:02 PMPPART
COMPLETE UNDERGROUND TRENCH IS OPEN Phone #: ###-#### Internet Inspection Request from: Lynn Cable
corr. made u/g ok for cover
ELE08-02292 Conference8/14/20088/15/20088/15/2008 11:37:00 AMADONE
###-#### Lee ok
ELE08-02057 Final8/15/20088/15/20088/15/2008 10:36:07 AMAPASS
THANKS JACK.......... Phone #: ###-#### Internet Inspection Request from: Bob Glenn
ESC08-00418 General Inspection8/15/20088/15/20088/15/2008 10:35:53 AMAPART
ELE08-02009 Electrical Rough-In8/15/20088/15/20088/15/2008 10:03:27 AMAPART
Phone #: ###-#### Internet Inspection Request from: Bryan McLaughlin walls anop
ELE08-02297 Conference8/14/20088/15/20088/15/2008 9:16:18 AMADONE
Jodi ###-#### ok
ELE08-02283 Rough-In Permanent Service8/14/20088/15/20088/15/2008 8:18:07 AMAFAIL
#80674,Q#8231AWQ. WIRED A NEW POWER PEDESTAL & PHONE CABINET FOR QWEST. JAMES ###-####. Phone #: ###-#### Internet Inspection Request from: Dan Mitchell
corr called 200.2(B) shall terminate GEC at neutral bus