FIR12-00247
| INSP-Sprinkler Rough-in | 8/15/2012 | 8/15/2012 | 8/15/2012 3:48:54 PM | P | CANC |
|
|
Concrete for thrust blocks not available. To be canceled per johnathan- this is for underground cover bld 10 Phone #: ###-####
|
BLD12-01393
| FIRE-Conference | 8/15/2012 | 8/15/2012 | 8/15/2012 2:59:03 PM | P | DONE |
|
|
I met with JP Burger/ESI about possible sprinkler protection in the parapats and at the new fire wall within the existing canopy. Approval from the architect is needed to move the fire wall and consultation with a fire sprinkler contractor is needed for the parapats.
|
FIR12-00435
| INSP-Sprinkler Rough-in | 8/15/2012 | 8/15/2012 | 8/15/2012 2:30:15 PM | P | PASS |
|
|
Underground supply piping is ok to cover.
|
FIR12-00429
| INSP-Supply line flush | 8/14/2012 | 8/15/2012 | 8/15/2012 2:29:14 PM | P | PASS |
|
|
Underground supply piping is ok to cover.
|
FIR12-00376
| INSP-Sprinkler Rough-in/Hydro | 8/14/2012 | 8/15/2012 | 8/15/2012 11:05:40 AM | A | FAIL |
|
|
Verified correct panel, battery size, phone lines 1 and 2 and sprinkler flow switch function. Also verified the smoke detector and audio/visual spacing. Stopped inspection after testing a bedroom smoke detector and it activated all of the notification devices which is not allowed. Also the facp needs to be connected to the tamper switches as shown on the approved drawings.
|
FIR12-00330
| INSP-Sprinkler Rough-in/Hydro | 8/14/2012 | 8/15/2012 | 8/15/2012 11:01:48 AM | P | CANC |
|
|
Please call 1/2hr prior to inspection. Dale is
the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
|
FIR12-00347
| INSP-Final Inspection | 8/14/2012 | 8/15/2012 | 8/15/2012 10:55:46 AM | A | FAIL |
|
|
Provide tamper switches, backflow certification, riser tags and add sprinkler protection in the riser room due to the wall that was built.
|
FIR12-00396
| INSP-Sprinkler Rough-in | 8/14/2012 | 8/15/2012 | 8/15/2012 10:54:38 AM | A | PASS |
|
|
The insulation still has not been repaired above rooms 103 and 127 and a hydro test is still required. However piping can be covered and the insulation checked at the final inspection.
|
BLD12-00618
| FIRE-Final Inspection | 8/15/2012 | 8/15/2012 | 8/15/2012 8:39:04 AM | P | PART |
|
|
A temporary occupancy is given until the two heads are changed to quick responce and the dead bolt hardware is removed as discussed.
|
FIR12-00390
| INSP-Final Inspection | 8/14/2012 | 8/15/2012 | 8/15/2012 8:37:55 AM | A | PART |
|
|
A temporary occupancy is given until the two heads are changed to quick responce.
|