Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR12-00247 INSP-Sprinkler Rough-in8/15/20128/15/20128/15/2012 3:48:54 PMPCANC
Concrete for thrust blocks not available. To be canceled per johnathan- this is for underground cover bld 10 Phone #: ###-####
BLD12-01393 FIRE-Conference8/15/20128/15/20128/15/2012 2:59:03 PMPDONE
I met with JP Burger/ESI about possible sprinkler protection in the parapats and at the new fire wall within the existing canopy. Approval from the architect is needed to move the fire wall and consultation with a fire sprinkler contractor is needed for the parapats.
FIR12-00435 INSP-Sprinkler Rough-in8/15/20128/15/20128/15/2012 2:30:15 PMPPASS
Underground supply piping is ok to cover.
FIR12-00429 INSP-Supply line flush8/14/20128/15/20128/15/2012 2:29:14 PMPPASS
Underground supply piping is ok to cover.
FIR12-00376 INSP-Sprinkler Rough-in/Hydro8/14/20128/15/20128/15/2012 11:05:40 AMAFAIL
Verified correct panel, battery size, phone lines 1 and 2 and sprinkler flow switch function. Also verified the smoke detector and audio/visual spacing. Stopped inspection after testing a bedroom smoke detector and it activated all of the notification devices which is not allowed. Also the facp needs to be connected to the tamper switches as shown on the approved drawings.
FIR12-00330 INSP-Sprinkler Rough-in/Hydro8/14/20128/15/20128/15/2012 11:01:48 AMPCANC
Please call 1/2hr prior to inspection. Dale is
the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
FIR12-00347 INSP-Final Inspection8/14/20128/15/20128/15/2012 10:55:46 AMAFAIL
Provide tamper switches, backflow certification, riser tags and add sprinkler protection in the riser room due to the wall that was built.
FIR12-00396 INSP-Sprinkler Rough-in8/14/20128/15/20128/15/2012 10:54:38 AMAPASS
The insulation still has not been repaired above rooms 103 and 127 and a hydro test is still required. However piping can be covered and the insulation checked at the final inspection.
BLD12-00618 FIRE-Final Inspection8/15/20128/15/20128/15/2012 8:39:04 AMPPART
A temporary occupancy is given until the two heads are changed to quick responce and the dead bolt hardware is removed as discussed.
FIR12-00390 INSP-Final Inspection8/14/20128/15/20128/15/2012 8:37:55 AMAPART
A temporary occupancy is given until the two heads are changed to quick responce.