Inspections for the day of: Friday, August 15, 2014.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD13-01792 FIRE-Final Inspection8/12/20148/15/20148/19/2014 4:52:48 PMAPART
Odie Phone #: ###-####-please give as much notice as possible so he can meet Phone #: ###-####
BLD13-01792 FIRE-Final Inspection8/12/20148/15/20148/19/2014 4:52:33 PMAPART
Odie Phone #: ###-####-please give as much notice as possible so he can meet Phone #: ###-####
BLD13-01793 FIRE-Final Inspection8/12/20148/15/20148/19/2014 4:52:18 PMAPART
Odie Phone #: ###-####
BLD13-00689 FIRE-Final Inspection8/12/20148/15/20148/19/2014 4:51:59 PMAPART
Odie Phone #: ###-####-please give as much notice as possible so he can meet
FIR14-00316 INSP-Sprinkler Rough-in/Hydro8/14/20148/15/20148/15/2014 4:31:37 PMAPART
Overhead hydrostatic testing passed. Need to provide plan modification to include field changes in branchline, main and sprinkler head locations and changes to type and number of sprinklers at several locations including the work room, kitchen, office, principal office, east classroom, music office, girls restroom, and storage closets.
FIR14-00260 INSP-Final Inspection8/15/20148/15/20148/15/2014 4:20:10 PMPPASS
Fire sprinkler permit finaled.
FIR14-00577 INSP-Final Inspection8/15/20148/15/20148/15/2014 4:19:35 PMPPART
Okay for cover at the main corridor ceiling.
FIR14-00277 INSP-Sprinkler Rough-in/Hydro8/14/20148/15/20148/15/2014 3:56:12 PMAPART
UG hydrostatic testing for both the remote FDC and the UG fire supply line completed satisfactory.
FIR13-00597 INSP-Final Inspection8/14/20148/15/20148/15/2014 3:21:59 PMAPART
Need to provide plan modification per inspection activity note dated 4/11/14.
FIR14-00204 INSP-Final Inspection8/12/20148/15/20148/15/2014 3:20:28 PMAPART
Items noted include; remove remainder of MP stations per the scope of work, new tamper switch supervision, remove remainder of old horns, clear obstructions at duct detector vent tubes, provide EOL testing for notification circuts on battery power. Duct detectors for unit shutdown tested okay.
FIR13-00533 INSP-Final Inspection8/12/20148/15/20148/15/2014 3:14:26 PMAPART
BLD14-01524 FIRE-Final Inspection8/14/20148/15/20148/15/2014 3:12:34 PMAPASS
Fire life safety finaled.
FIR14-00368 INSP-Final Inspection8/15/20148/15/20148/15/2014 3:12:04 PMPPASS
Scope of fire sprinkler work passed final walkthrough. Permit finaled.
FIR14-00123 INSP-Final Inspection8/12/20148/15/20148/15/2014 3:11:22 PMAPASS
Fire alarm permit finaled. Inspection passed.
FIR14-00062 INSP-Final Inspection8/12/20148/15/20148/15/2014 3:10:33 PMAPASS
Fire alarm work passed inspection. Permit finaled.
FIR14-00262 INSP-Final Inspection8/12/20148/15/20148/15/2014 3:09:18 PMAPASS
Inspection and functional testing passed. Fire alarm permit finaled.
FIR14-00263 INSP-Final Inspection8/12/20148/15/20148/15/2014 3:08:03 PMAPASS
Fire alarm work passed inspection.