ELE16-02399
| Electrical Rough-In | 8/15/2016 | 8/15/2016 | 8/15/2016 2:53:08 PM | P | PASS |
|
|
Underground Phone #: ###-#### Inspection requested via web by Christy Cheney underground building A pour 2 and concrete encased electrode ok cover
|
ELE16-02621
| Electrical Rough-In | 8/11/2016 | 8/15/2016 | 8/15/2016 2:52:08 PM | P | CANC |
|
|
rough in so idaho power will restore Phone #: ###-#### Inspection requested via web by Randy Fletcher needed p/s
|
ELE16-02621
| Permanent Service | 8/15/2016 | 8/15/2016 | 8/15/2016 2:51:46 PM | P | PASS |
|
|
rough in so idaho power will restore Phone #: ###-#### Inspection requested via web by Randy Fletcher p/s u/g rec ok
|
ELE16-02155
| Final | 8/12/2016 | 8/15/2016 | 8/15/2016 2:12:59 PM | P | PART |
|
|
Inspection requested via web by CHRIS CARMINE classroom only/ need area of classification for storage/shop, for receptacles that were added there is clear ventilation in this room and power saws.
|
ELE16-02645
| Electrical Rough-In | 8/15/2016 | 8/15/2016 | 8/15/2016 1:36:19 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by CHRIS CARMINE rough-in for mod1-b whole rewire ok
|
ELE16-01896
| Final | 8/15/2016 | 8/15/2016 | 8/15/2016 1:07:59 PM | P | PASS |
|
|
code 1234. ready now Phone #: ###-#### Inspection requested via web by Bob Glenn final ok
|
ELE16-02641
| Electrical Rough-In | 8/14/2016 | 8/15/2016 | 8/15/2016 12:17:23 PM | A | PASS |
|
|
lock box is on staircase banister near door. code is 1013 any questions please call Phone #: ###-#### Inspection requested via web by michael hunt walls only as noted on print only ok cover
|
ELE16-01738
| Final | 8/12/2016 | 8/15/2016 | 8/15/2016 9:29:51 AM | A | FAIL |
|
|
PLEASE CALL MANAGER OF FACILITY AT ###-#### HIS OFFICE IS AT THE MAIN LOBBY. ALLEN THE ELECTRICIAN PHONE NUMBER IS ###-#### Phone #: ###-#### Inspection requested via web by SHAWN TOMLINSON 314.25 cover required for pool pump 680.20 (c)GFCI protection required for all pool pumps 680.22 GFCI protection for underwater luminaires 680.26(B) pump shall be bonded POOL NOT TO BE USED UNTIL ITEMS FIXED
|
ELE16-00261
| Final | 8/8/2016 | 8/15/2016 | 8/15/2016 8:37:15 AM | A | FAIL |
|
|
Rachelle Phone #: ###-#### 680 GFCI protection required for hot tubs (breaker in-op) 356.12 LFNC shall not be used where subject to physical damage
|
ELE16-01643
| Final | 8/15/2016 | 8/15/2016 | 8/15/2016 8:35:14 AM | P | FAIL |
|
|
please call for garage code. thanks Phone #: ###-#### Inspection requested via web by Jarod Murray 680 GFCI protection required for Hot Tubs(breaker in-op) 325.12 type LFNC shall not be installed where subject to physical damage.
|
ELE16-02636
| Conference | 8/12/2016 | 8/15/2016 | 8/15/2016 8:18:40 AM | A | CANC |
|
|
Dean Phone #: ###-#### called and waited 10 mins, will have to reschedule
|