Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE16-02399 Electrical Rough-In8/15/20168/15/20168/15/2016 2:53:08 PMPPASS
Underground Phone #: ###-#### Inspection requested via web by Christy Cheney underground building A pour 2 and concrete encased electrode ok cover
ELE16-02621 Electrical Rough-In8/11/20168/15/20168/15/2016 2:52:08 PMPCANC
rough in so idaho power will restore Phone #: ###-#### Inspection requested via web by Randy Fletcher
needed p/s
ELE16-02621 Permanent Service8/15/20168/15/20168/15/2016 2:51:46 PMPPASS
rough in so idaho power will restore Phone #: ###-#### Inspection requested via web by Randy Fletcher
p/s u/g rec ok
ELE16-02155 Final8/12/20168/15/20168/15/2016 2:12:59 PMPPART
Inspection requested via web by CHRIS CARMINE
classroom only/ need area of classification for storage/shop, for receptacles that were added there is clear ventilation in this room and power saws.
ELE16-02645 Electrical Rough-In8/15/20168/15/20168/15/2016 1:36:19 PMPPASS
Phone #: ###-#### Inspection requested via web by CHRIS CARMINE
rough-in for mod1-b whole rewire ok
ELE16-01896 Final8/15/20168/15/20168/15/2016 1:07:59 PMPPASS
code 1234. ready now Phone #: ###-#### Inspection requested via web by Bob Glenn
final ok
ELE16-02641 Electrical Rough-In8/14/20168/15/20168/15/2016 12:17:23 PMAPASS
lock box is on staircase banister near door. code is 1013
any questions please call Phone #: ###-#### Inspection requested via web by michael hunt
walls only as noted on print only ok cover
ELE16-01738 Final8/12/20168/15/20168/15/2016 9:29:51 AMAFAIL
PLEASE CALL MANAGER OF FACILITY AT ###-#### HIS OFFICE IS AT THE MAIN LOBBY. ALLEN THE ELECTRICIAN PHONE NUMBER IS ###-#### Phone #: ###-#### Inspection requested via web by SHAWN TOMLINSON
314.25 cover required for pool pump
680.20 (c)GFCI protection required for all pool pumps
680.22 GFCI protection for underwater luminaires
680.26(B) pump shall be bonded
POOL NOT TO BE USED UNTIL ITEMS FIXED
ELE16-00261 Final8/8/20168/15/20168/15/2016 8:37:15 AMAFAIL
Rachelle Phone #: ###-####
680 GFCI protection required for hot tubs (breaker in-op)
356.12 LFNC shall not be used where subject to physical damage
ELE16-01643 Final8/15/20168/15/20168/15/2016 8:35:14 AMPFAIL
please call for garage code. thanks Phone #: ###-#### Inspection requested via web by Jarod Murray
680 GFCI protection required for Hot Tubs(breaker in-op)
325.12 type LFNC shall not be installed where subject to physical damage.
ELE16-02636 Conference8/12/20168/15/20168/15/2016 8:18:40 AMACANC
Dean Phone #: ###-####
called and waited 10 mins, will have to reschedule