FIR15-00727
| INSP-Sprinkler Rough-in/Hydro | 8/15/2016 | 8/15/2016 | 8/15/2016 3:02:17 PM | P | PART |
|
|
Rough to cover inspection for overhead fire sprinkler piping above restrooms in the commercial kitchen area complete, overhead piping above restroom hardlids in commercial kitchen approved for cover. Rough to cover inspection for overhead fire sprinkler piping located above the soffits on level 4 complete, overhead fire sprinkler piping located above level 4 soffits approved for cover. Rough in inspections for level 1 wet system complete, level 3 wet system complete, level 2 dry system complete as well as stairwells.
|
FIR15-00304
| INSP-Sprinkler Rough-in/Hydro | 8/15/2016 | 8/15/2016 | 8/15/2016 10:07:18 AM | A | PASS |
|
|
Rough to cover inspection complete for level 1, overhead fire sprinkler piping on level 1 approved for cover. 200 psi hydrostatic test for overhead fire sprinkler piping located on level 1 complete.
|
FIR16-00452
| INSP-Final Inspection | 8/15/2016 | 8/15/2016 | 8/15/2016 10:05:51 AM | A | PASS |
|
|
Final fire alarm inspection passed/complete.
|
FIR16-00452
| INSP-Alarm Testing | 8/12/2016 | 8/15/2016 | 8/15/2016 10:04:25 AM | A | CANC |
|
|
Inspection request was for a final fire alarm inspection, not testing. This inspection request cancelled and the correct inspection request will be generated.
|
FIR16-00162
| INSP-Sprinkler Rough-in/Hydro | 8/15/2016 | 8/15/2016 | 8/15/2016 8:31:36 AM | A | PART |
|
|
Partial rough to cover inspection for overhead fire sprinkler piping complete, notated city approved drawings with blue highlighter and red ink overhead fire sprinkler piping approved for cover.
|