Inspections for the day of: Wednesday, August 15, 2018.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-01608 Temporary Service8/15/20188/15/20188/15/2018 2:46:12 PMPFAIL
please call Corey Phone #: ###-#### Inspection requested via web by Kevin Perez
Temp service requires seperate permit
ELE18-02656 Final8/14/20188/15/20188/15/2018 2:17:22 PMPPASS
Phone #: ###-#### Inspection requested via web by Cortney Hopper Final ok
ELE18-02656 Electrical Rough-In8/15/20188/15/20188/15/2018 2:14:34 PMPPASS
Phone #: ###-#### Inspection requested via web by Cortney Hopper
All wiring surface mounted for lighting. Receptacle fished in wall. Rough in ok
ELE18-00502 Final8/13/20188/15/20188/15/2018 1:52:50 PMPPASS
homeowner to be home Phone #: ###-#### Inspection requested via web by Kevin Koomler Final ok
ELE18-03068 Electrical Rough-In8/15/20188/15/20188/15/2018 1:17:26 PMPPASS
Garage code 1957e Phone #: ###-#### Inspection requested via web by Alan Lusk
Rough in ok cover p/s u/g n ok
ELE18-02177 Final8/15/20188/15/20188/15/2018 12:53:03 PMPFAIL
Garage code 1957e Phone #: ###-#### Inspection requested via web by Alan Lusk
110.3- Areas not complete- garage receptacles not working, 1/2 of kitchen and pantry receptacles not working, disposal cord, hood hook up.
210.52(B)- Kitchen counter top receptacles, no point measured along wall line shall be more than 24" from a receptacle outlet. kitchen window wall 5'5" between receptacles.
314.25- All boxes shall have covers. Bathroom vanity lights level 1&2, Device cover level 1 brick wall and level 3 switch covers.
ELE18-03106 Rough-In Permanent Service8/15/20188/15/20188/15/2018 11:18:10 AMAPASS
2089899410....

Call John if any problems Inspection requested via web by John Harvey
Service rough in only. No wiring in house yet, temp receptacles not in yet. p/s u/g n ok
ELE18-03096 Final8/14/20188/15/20188/15/2018 10:55:15 AMAPASS
Robert Phone #: ###-#### Final ok
ELE18-03096 Electrical Rough-In8/15/20188/15/20188/15/2018 10:38:50 AMPPASS
Robert Phone #: ###-####
Rough in ok
ELE18-03061 Rough-In Permanent Service8/15/20188/15/20188/15/2018 10:38:01 AMAPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn
Rough in ok cover
ELE18-02664 Rough-In Permanent Service8/15/20188/15/20188/15/2018 10:14:37 AMAPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn
Rough in ok cover p/s u/g n ok
ELE18-02479 Electrical Rough-In8/15/20188/15/20188/15/2018 9:38:19 AMAPART
Wall rough-in inspection for level 10 CH2M in One Cap building
Contact Jon Novak
Thank you Phone #: ###-#### Inspection requested via web by Tom Betty
Hold on MFP wall and to west due to boxes behind new wall shall be abandoned prior to cover. Rest of walls rough in ok cover.
ELE17-04065 Final8/14/20188/15/20188/14/2018 3:22:04 PMAPASS
Danny is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen
Corrections complete. Final ok