ELE15-01210
| ELE-Aging Inspection | 8/15/2019 | 8/15/2019 | 8/15/2019 2:46:22 PM | | FAIL |
|
|
Waiting on contractor
|
ELE19-02900
| Electrical Rough-In | 8/15/2019 | 8/15/2019 | 8/15/2019 2:39:37 PM | P | PASS |
|
|
Joel Hopkins is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce Phase 1 basement south corridor 1st 4 rooms on left and last 2 on left wall and grid rough in ok cover
|
ELE19-02028
| Electrical Rough-In | 8/15/2019 | 8/15/2019 | 8/15/2019 1:52:11 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton 330.30- MC shall be secured with in 12" of a box, not including fixture whips. * Popped MC in S,E, office still not repaired. Reception/ lobby area being grouted at time of inspection. Recall when accessible.
|
ELE19-02407
| Final | 8/15/2019 | 8/15/2019 | 8/15/2019 1:19:40 PM | P | PASS |
|
|
Final on 4th floor HVAC. Randy is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen Final ok
|
ELE19-02510
| Final | 8/14/2019 | 8/15/2019 | 8/15/2019 11:50:28 AM | A | FAIL |
|
|
HO on site Phone #: ###-#### Inspection requested via web by Darryn Coburn 110.12(A)- Unused openings shall be closed by approved means. KO seal in bottom of panel, Connector needed on grounding electrode conductor at exterior disconnect. 300.4(G)- Insulating bushings shall be installed where #4 or larger enter an enclosure.
|
ELE19-03009
| Final | 8/14/2019 | 8/15/2019 | 8/15/2019 10:52:36 AM | A | PASS |
|
|
install complete per approved plans; approved plans and journeyman on site Phone #: ###-#### Inspection requested via web by Ryan King Final ok
|
ELE19-03011
| Electrical Rough-In | 8/14/2019 | 8/15/2019 | 8/15/2019 10:30:32 AM | A | PASS |
|
|
listing inspection for solar equipment first day of panel install Phone #: ###-#### Inspection requested via web by Ryan King Listings confirmed. Rough in ok
|
ELE19-02082
| Final | 8/14/2019 | 8/15/2019 | 8/15/2019 10:22:13 AM | A | FAIL |
|
|
garage code 7530 Phone #: ###-#### Inspection requested via web by Darryn Coburn Must have access to all electrical boxes. Doors stacked in garage blocking access. Recall when all is accessible.
|
ELE19-02292
| Final | 8/14/2019 | 8/15/2019 | 8/15/2019 10:06:29 AM | A | PASS |
|
|
garage code 2468 Phone #: ###-#### Inspection requested via web by Darryn Coburn Final ok
|
ELE19-02291
| Final | 8/14/2019 | 8/15/2019 | 8/15/2019 9:53:09 AM | A | PASS |
|
|
garage code 2468 Phone #: ###-#### Inspection requested via web by Darryn Coburn Final ok
|
ELE19-02381
| Final | 8/14/2019 | 8/15/2019 | 8/15/2019 9:20:06 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Winters LLC Final ok
|