MEC01-01305
| MEC-Aging Inspection | 8/16/2001 | 8/16/2001 | 8/16/2001 12:00:00 AM | | PASS |
|
|
finale 8/16/2001 11:02:22 AM d by 406 on 5-3-01 8/16/2001 11:02:46 AM
|
FIR01-00443
| INSP-Sprinkler Rough-in | 8/16/2001 | 8/16/2001 | 8/16/2001 12:00:00 AM | A | PART |
|
|
Added by Inspector: 406 On 8/16/2001 10:54:08 AM OK to cover supply line
|
BLD00-02660
| FIRE-Final Inspection | 8/15/2001 | 8/16/2001 | 8/16/2001 12:00:00 AM | A | FAIL |
|
|
Final Fail C/N issued 8/16/2001 10:21:34 AM
|
FIR01-00314
| INSP-Supply line flush | 8/15/2001 | 8/16/2001 | 8/16/2001 12:00:00 AM | A | PART |
|
|
OK to cover supply line 8/16/2001 11:18:00 AM
|
BLD01-01601
| FIRE-Conference | 8/15/2001 | 8/16/2001 | 8/16/2001 12:00:00 AM | A | PASS |
|
|
Conf with contr regarding fire/life safety issues 8/16/2001 11:36:13 AM
|
BLD01-01695
| FIRE-Sprinkler Rough-in | 8/15/2001 | 8/16/2001 | 8/16/2001 12:00:00 AM | A | CANC |
|
|
###-####
|
BLD01-01489
| FIRE-Final Inspection | 8/15/2001 | 8/16/2001 | 8/16/2001 12:00:00 AM | A | FAIL |
|
|
Final Fail Fire hydrant involved in drop off lane 8/16/2001 10:06:18 AM
|
BLD00-02817
| FIRE-Final Inspection | 8/15/2001 | 8/16/2001 | 8/16/2001 12:00:00 AM | P | CANC |
|
|
|
BLD00-03498
| FIRE-Final Inspection | 8/16/2001 | 8/16/2001 | 8/16/2001 12:00:00 AM | P | PASS |
|
|
Reinsp OK for permanant occupancy 8/16/2001 4:01:36 PM
|
FIR01-00388
| INSP-Alarm Testing | 8/16/2001 | 8/16/2001 | 8/16/2001 12:00:00 AM | P | FAIL |
|
|
Final Fail AHU detectors not ready to test. Elevator not operating properly 8/16/2001 2:58:02 PM
|
BLD00-03041
| FIRE-Final Inspection | 8/16/2001 | 8/16/2001 | 8/16/2001 12:00:00 AM | P | FAIL |
|
|
Reinsp Fail Modify supply registers in several rooms so air does not blow on detectors that are within 3 ft 8/16/2001 3:20:31 PM
|
BLD01-01080
| FIRE-Final Inspection | 8/16/2001 | 8/16/2001 | 8/16/2001 12:00:00 AM | P | FAIL |
|
|
Reinsp Fail emergrency lights not operating 8/17/2001 3:59:58 PM
|