ELE02-00008
| Final | 8/15/2002 | 8/16/2002 | 8/16/2002 12:00:00 AM | A | PASS |
|
|
RON ###-#### SITE LIGHTING PERMIT WAS TAKEN OUT (SUPERIOR ELE TOOK IT OUT) IF ANY PROBLEMS PLEASE CANTACT RON ok 8/15/2002 5:01:34 PM
|
ELE02-02098
| Rough-In Permanent Service | 8/15/2002 | 8/16/2002 | 8/16/2002 12:00:00 AM | A | NH |
|
|
Scheduled by a contractor via Hello! on 08/15/2002 at 13:53:20. Contact: . notice posted 8/16/2002 10:40:29 AM
|
ELE02-02537
| Rough-In Permanent Service | 8/15/2002 | 8/16/2002 | 8/16/2002 12:00:00 AM | A | PASS |
|
|
###-#### detached garage garage and u/g ok 8/16/2002 2:10:58 PM
|
ELE02-00623
| Electrical Rough-In | 8/15/2002 | 8/16/2002 | 8/16/2002 12:00:00 AM | A | PART |
|
|
###-#### DUAINE no r/i conference ok only 8/16/2002 11:16:46 AM
|
ELE02-01424
| Final | 8/15/2002 | 8/16/2002 | 8/16/2002 12:00:00 AM | A | NR |
|
|
Scheduled by a contractor via Hello! on 08/15/2002 at 16:39:34. Contact: ###-####. 8/16/2002 10:39:59 AM no acces disconnects locked and same corrections as 805 s shoshone talked with contractor 8/16/2002 12:30:35 PM
|
ELE02-01917
| Electrical Rough-In | 8/16/2002 | 8/16/2002 | 8/16/2002 12:00:00 AM | A | FAIL |
|
|
cor. posted met with contractor and PLass 110.3(B) max 15 amp feed too fan coil unit, 386.22 wire fill shall not exceed what raceway is designed for, 300.16 shall provide a terminal fitting for abrasion where cable exits raceway
|
ELE02-02374
| Final | 8/16/2002 | 8/16/2002 | 8/16/2002 12:00:00 AM | P | PASS |
|
|
ok
|
ELE02-02374
| Electrical Rough-In | 8/16/2002 | 8/16/2002 | 8/16/2002 12:00:00 AM | P | CANC |
|
|
###-#### wayne or jim no r/i see added final
8/16/2002 6:22:21 PM
|
ELE02-01900
| Electrical Rough-In | 8/16/2002 | 8/16/2002 | 8/16/2002 12:00:00 AM | P | PART |
|
|
Scheduled by a contractor via Hello! on 08/16/2002 at 08:04:15. Contact: . u/g to garage ok 8/16/2002 3:13:39 PM
|
ELE02-02559
| Rough-In Permanent Service | 8/16/2002 | 8/16/2002 | 8/16/2002 12:00:00 AM | P | PART |
|
|
###-#### dan master bath only ok for r/i 8/16/2002 3:50:35 PM
|
ELE02-02556
| Electrical Rough-In | 8/16/2002 | 8/16/2002 | 8/16/2002 12:00:00 AM | P | PART |
|
|
Scheduled by a contractor via Hello! on 08/16/2002 at 08:17:58. Contact: ###-####. part walls and ceiling N W bed rm 8/16/2002 4:29:10 PM
|
ELE02-02480
| Permanent Service | 8/16/2002 | 8/16/2002 | 8/16/2002 12:00:00 AM | P | PASS |
|
|
###-#### p/s only Romar did not wire new addition
p/s o/h rec ok 8/16/2002 5:20:41 PM
|
ELE02-02197
| Electrical Rough-In | 8/15/2002 | 8/16/2002 | 8/16/2002 12:00:00 AM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 08/15/2002 at 16:20:02. Contact: ###-####. cor. posted met with owner250.8,110.3 (B) breakers, 300.5, 250.52(C), 352.46and 300.4(F), 110.14(B) insulation for splices jbox, 110.26 cleraence in front of panels in garage 8/16/2002 6:53:00 PM
|