ELE04-01952
| Final | 8/12/2004 | 8/16/2004 | 8/16/2004 12:00:00 AM | A | PASS |
|
|
Call Mike Balls ###-#### or page me for ; Phone #: ###-#### Internet Inspection Request from: Ron Peterson ok final service for d ram site 8/16/2004 9:05:25 AM
|
ELE04-01952
| Final | 8/12/2004 | 8/16/2004 | 8/16/2004 12:00:00 AM | A | PASS |
|
|
Call Mike Balls ###-#### or page me for ; Phone #: ###-#### Internet Inspection Request from: Ron Peterson ok final service for d ram site 8/16/2004 9:05:25 AM
|
ELE04-02484
| Electrical Rough-In | 8/13/2004 | 8/16/2004 | 8/16/2004 12:00:00 AM | A | PASS |
|
|
###-#### - allen ok cover ri
p/s u/g n ok 8/16/2004 11:59:43 AM
|
ELE04-02398
| Electrical Rough-In | 8/13/2004 | 8/16/2004 | 8/16/2004 12:00:00 AM | A | PASS |
|
|
Mark; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes ok cover ri 8/16/2004 11:48:18 AM
|
ELE04-01952
| Final | 8/12/2004 | 8/16/2004 | 8/16/2004 12:00:00 AM | A | PASS |
|
|
Call Mike Balls ###-#### or page me for ; Phone #: ###-#### Internet Inspection Request from: Ron Peterson ok final service for d ram site 8/16/2004 9:05:25 AM
|
ELE04-01952
| Final | 8/12/2004 | 8/16/2004 | 8/16/2004 12:00:00 AM | A | PASS |
|
|
Call Mike Balls ###-#### or page me for ; Phone #: ###-#### Internet Inspection Request from: Ron Peterson ok final service for d ram site 8/16/2004 9:05:25 AM
|
ELE04-01952
| Final | 8/12/2004 | 8/16/2004 | 8/16/2004 12:00:00 AM | A | PASS |
|
|
Call Mike Balls ###-#### or page me for ; Phone #: ###-#### Internet Inspection Request from: Ron Peterson ok final service for d ram site 8/16/2004 9:05:25 AM
|
ELE04-01952
| Final | 8/12/2004 | 8/16/2004 | 8/16/2004 12:00:00 AM | A | PASS |
|
|
Call Mike Balls ###-#### or page me for ; Phone #: ###-#### Internet Inspection Request from: Ron Peterson ok final service for d ram site 8/16/2004 9:05:25 AM
|
ELE04-01952
| Final | 8/12/2004 | 8/16/2004 | 8/16/2004 12:00:00 AM | A | PASS |
|
|
Call Mike Balls ###-#### or page me for ; Phone #: ###-#### Internet Inspection Request from: Ron Peterson ok final service for d ram site 8/16/2004 9:05:25 AM
|
ELE04-01952
| Final | 8/12/2004 | 8/16/2004 | 8/16/2004 12:00:00 AM | A | PASS |
|
|
Call Mike Balls ###-#### or page me for ; Phone #: ###-#### Internet Inspection Request from: Ron Peterson ok final service for d ram site 8/16/2004 9:05:25 AM
|
ELE04-02484
| Permanent Service | 8/16/2004 | 8/16/2004 | 8/16/2004 12:00:00 AM | A | CANC |
|
|
p/s u/g n ok
|
ELE04-02412
| Permanent Service | 8/16/2004 | 8/16/2004 | 8/16/2004 12:00:00 AM | P | PASS |
|
|
p/s u/g n ok
|
ELE04-02502
| Final | 8/16/2004 | 8/16/2004 | 8/16/2004 12:00:00 AM | P | CANC |
|
|
###-#### - jim - note: hot tub no hot tub installed contractor called for a permit not inspection 8/16/2004 3:51:53 PM
|
ELE04-01978
| Final | 8/16/2004 | 8/16/2004 | 8/16/2004 12:00:00 AM | P | FAIL |
|
|
WARREN; Phone #: ###-#### Internet Inspection Request from: Annette Moore corrections nectable wire size for 225amp shall be 4/0, nec250.66 grounding electroode conductor size for 4/0 shall be 2 cu bc reuires 2 ground rods 6ft or more apart . 8/16/2004 3:33:45 PM
|
ELE04-00009
| ELE-Request for Extension | 8/16/2004 | 8/16/2004 | 8/16/2004 12:00:00 AM | P | NR |
|
|
Quinn; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes ok extention 8/16/2004 12:20:23 PM
|
ELE04-02416
| Electrical Rough-In | 8/16/2004 | 8/16/2004 | 8/16/2004 12:00:00 AM | P | CANC |
|
|
lynn; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles contractor cancelled 8/16/2004 1:05:16 PM
|
ELE04-02402
| Electrical Rough-In | 8/16/2004 | 8/16/2004 | 8/16/2004 12:00:00 AM | P | PASS |
|
|
dwayne--call 1st before insp about 1/2 hr; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok cover ri 8/16/2004 2:26:10 PM
|
ELE04-02106
| Electrical Rough-In | 8/16/2004 | 8/16/2004 | 8/16/2004 12:00:00 AM | P | NR |
|
|
curt; Phone #: ###-#### Internet Inspection Request from: Annette Moore not ready not make up curc. wrong out side gfci did not finish inspection. called need to meet wireman on site. 8/16/2004 2:28:20 PM
|
ELE04-01760
| Final | 8/16/2004 | 8/16/2004 | 8/16/2004 12:00:00 AM | P | CANC |
|
|
jim ###-####
|
ELE04-02412
| Electrical Rough-In | 8/16/2004 | 8/16/2004 | 8/16/2004 12:00:00 AM | P | PASS |
|
|
jay; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok cover ri 8/16/2004 4:31:37 PM
|
ELE04-01761
| Final | 8/16/2004 | 8/16/2004 | 8/16/2004 12:00:00 AM | P | FAIL |
|
|
jim; Phone #: ###-#### Internet Inspection Request from: Annette Moore fail corrections nec 210.70(A)(3), switched light in equipment rm & nec 210.52(C)(1) outlt spacing kit. over 48 inchs ( gave contractor survey regarding this) 8/16/2004 1:00:36 PM
|