Inspections for the day of: Thursday, August 16, 2007.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-00609 Final8/16/20078/16/20078/16/2007 3:12:51 PMPPASS
corrections have been made and its ready for final inspection (at least temp occup)please call with any questions
Brad Phone #: ###-#### Internet Inspection Request from: Brad Baker called contr,corrections made, ok to final, no occ card to sign
ELE07-01473 Electrical Rough-In8/16/20078/16/20078/16/2007 3:02:10 PMPPASS
NOTE: UIFER Phone #: ###-#### ok to backfill gec
ELE07-01657 Rough-In Permanent Service8/16/20078/16/20078/16/2007 2:17:06 PMPFAIL
Phone #: ###-#### called contr, only part corrections made, didn't mean to call for inspection yet, see edited corr notice on door, only 1 1/4" taken care of
ELE07-02869 Electrical Rough-In8/16/20078/16/20078/16/2007 1:51:28 PMPCANC
Tom; Phone #: ###-#### Internet Inspection Request from: Hattie James see rip, wrong type request
ELE07-02869 Rough-In Permanent Service8/16/20078/16/20078/16/2007 1:51:02 PMPPASS
Tom; Phone #: ###-#### Internet Inspection Request from: Hattie James ric ok, p/s u/g n ok (5 meters)
ELE07-02760 Electrical Rough-In8/16/20078/16/20078/16/2007 12:58:53 PMPPASS
Butch; Phone #: ###-#### Internet Inspection Request from: Hattie James ok to pour concrete encased electrode
ELE07-02041 Final8/16/20078/16/20078/16/2007 12:35:41 PMPPASS
Scheduled by a contractor via Hello! on 8/16/2007 at 9:51:28 AM. Contact: ###-####. ok to final, called about plates for recpts
ELE07-02760 Permanent Service8/15/20078/16/20078/16/2007 11:39:23 AMAPART
Butch; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt service ok, but need to install concrete encased electrode and inspect before switch power, house ric ok checked outlets
ELE07-02855 Electrical Rough-In8/15/20078/16/20078/16/2007 10:43:09 AMAPASS
louis ###-####-underground inspection please u/g to pool ok to cover, bonding ok
ELE07-01762 Electrical Rough-In8/15/20078/16/20078/16/2007 10:09:08 AMAFAIL
ceiling grid; in lobby where new ceiling is; Tim; Phone #: ###-#### Internet Inspection Request from: Hattie James called, left corr notice, nec 110.12(A) unused openings in boxes shall be closed, 330.30(B) mc cable shall be secured within12" of box, 300.11(A) cables and raceways shall not be supported by grid, BCC low voltage cables shall not be supported bt grid
ELE07-02499 Permanent Service8/16/20078/16/20078/16/2007 9:36:32 AMAPASS
p/s o/h rec ok
ELE07-02499 Electrical Rough-In8/15/20078/16/20078/16/2007 9:35:14 AMAPASS
Sam; call half hour prior for access; Phone #: ###-#### Internet Inspection Request from: Hattie James ric ok service area
ELE07-02841 Final8/16/20078/16/20078/16/2007 9:18:47 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Kathy Briggs ok to final
ELE06-03186 Final8/16/20078/16/20078/16/2007 8:40:08 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Kathy Briggs ok to final
ELE07-01119 Conference8/15/20078/16/20078/16/2007 8:09:56 AMADONE
Dave; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt met elect to review support for pendant type fixtures mounted box to box from ceiling
ELE07-02506 Final8/14/20078/16/20078/15/2007 8:42:48 AMACANC
Phone #: ###-#### Internet Inspection Request from: Scott Abbott Inspection cancelled from web by: Scott Abbott