ELE07-00609
| Final | 8/16/2007 | 8/16/2007 | 8/16/2007 3:12:51 PM | P | PASS |
|
|
corrections have been made and its ready for final inspection (at least temp occup)please call with any questions Brad Phone #: ###-#### Internet Inspection Request from: Brad Baker called contr,corrections made, ok to final, no occ card to sign
|
ELE07-01473
| Electrical Rough-In | 8/16/2007 | 8/16/2007 | 8/16/2007 3:02:10 PM | P | PASS |
|
|
NOTE: UIFER Phone #: ###-#### ok to backfill gec
|
ELE07-01657
| Rough-In Permanent Service | 8/16/2007 | 8/16/2007 | 8/16/2007 2:17:06 PM | P | FAIL |
|
|
Phone #: ###-#### called contr, only part corrections made, didn't mean to call for inspection yet, see edited corr notice on door, only 1 1/4" taken care of
|
ELE07-02869
| Electrical Rough-In | 8/16/2007 | 8/16/2007 | 8/16/2007 1:51:28 PM | P | CANC |
|
|
Tom; Phone #: ###-#### Internet Inspection Request from: Hattie James see rip, wrong type request
|
ELE07-02869
| Rough-In Permanent Service | 8/16/2007 | 8/16/2007 | 8/16/2007 1:51:02 PM | P | PASS |
|
|
Tom; Phone #: ###-#### Internet Inspection Request from: Hattie James ric ok, p/s u/g n ok (5 meters)
|
ELE07-02760
| Electrical Rough-In | 8/16/2007 | 8/16/2007 | 8/16/2007 12:58:53 PM | P | PASS |
|
|
Butch; Phone #: ###-#### Internet Inspection Request from: Hattie James ok to pour concrete encased electrode
|
ELE07-02041
| Final | 8/16/2007 | 8/16/2007 | 8/16/2007 12:35:41 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 8/16/2007 at 9:51:28 AM. Contact: ###-####. ok to final, called about plates for recpts
|
ELE07-02760
| Permanent Service | 8/15/2007 | 8/16/2007 | 8/16/2007 11:39:23 AM | A | PART |
|
|
Butch; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt service ok, but need to install concrete encased electrode and inspect before switch power, house ric ok checked outlets
|
ELE07-02855
| Electrical Rough-In | 8/15/2007 | 8/16/2007 | 8/16/2007 10:43:09 AM | A | PASS |
|
|
louis ###-####-underground inspection please u/g to pool ok to cover, bonding ok
|
ELE07-01762
| Electrical Rough-In | 8/15/2007 | 8/16/2007 | 8/16/2007 10:09:08 AM | A | FAIL |
|
|
ceiling grid; in lobby where new ceiling is; Tim; Phone #: ###-#### Internet Inspection Request from: Hattie James called, left corr notice, nec 110.12(A) unused openings in boxes shall be closed, 330.30(B) mc cable shall be secured within12" of box, 300.11(A) cables and raceways shall not be supported by grid, BCC low voltage cables shall not be supported bt grid
|
ELE07-02499
| Permanent Service | 8/16/2007 | 8/16/2007 | 8/16/2007 9:36:32 AM | A | PASS |
|
|
p/s o/h rec ok
|
ELE07-02499
| Electrical Rough-In | 8/15/2007 | 8/16/2007 | 8/16/2007 9:35:14 AM | A | PASS |
|
|
Sam; call half hour prior for access; Phone #: ###-#### Internet Inspection Request from: Hattie James ric ok service area
|
ELE07-02841
| Final | 8/16/2007 | 8/16/2007 | 8/16/2007 9:18:47 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Kathy Briggs ok to final
|
ELE06-03186
| Final | 8/16/2007 | 8/16/2007 | 8/16/2007 8:40:08 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Kathy Briggs ok to final
|
ELE07-01119
| Conference | 8/15/2007 | 8/16/2007 | 8/16/2007 8:09:56 AM | A | DONE |
|
|
Dave; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt met elect to review support for pendant type fixtures mounted box to box from ceiling
|
ELE07-02506
| Final | 8/14/2007 | 8/16/2007 | 8/15/2007 8:42:48 AM | A | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: Scott Abbott Inspection cancelled from web by: Scott Abbott
|