FIR07-00482
| INSP-Final Inspection | 8/10/2007 | 8/16/2007 | 8/16/2007 4:30:02 PM | P | NR |
|
|
Need completion of the OH hydrostatic tests and related riser supervision testing prior to final.
|
FIR07-00482
| INSP-Sprinkler Rough-in/Hydro | 8/10/2007 | 8/16/2007 | 8/16/2007 4:28:03 PM | P | PART |
|
|
Verified corrections noted at the previous inspection have been completed, hydrostatic testing failed due to pressures below 200 psi at the guages.
|
FIR06-00007
| INSP-Final Inspection | 8/14/2007 | 8/16/2007 | 8/16/2007 4:00:16 PM | A | PART |
|
|
Retested items on the first floor in need of correction, doors need adjusted at the service elevator lobby, missing a HD for the elevator machine room, two SD at the link relocated while on site, several items remain to be tested at the 2nd floor.
|
FIR07-00643
| INSP-Sprinkler Rough-in/Hydro | 8/15/2007 | 8/16/2007 | 8/16/2007 3:54:46 PM | A | FAIL |
|
|
Heads at several locations including along the west wall of the sales floor exceed maximum allowed spacing for OH group 2 as designed. The hydrostatic test passed.
|
BLD07-01426
| FIRE-Final Inspection | 8/15/2007 | 8/16/2007 | 8/16/2007 12:58:47 PM | A | CANC |
|
|
Overbooked, no time available to complete this inspection today.
|
FIR07-00233
| INSP-Sprinkler Rough-in | 8/15/2007 | 8/16/2007 | 8/16/2007 12:56:34 PM | P | CANC |
|
|
Overbooked, no time available for this inspection today.
|
FIR07-00603
| INSP-Final Inspection | 8/15/2007 | 8/16/2007 | 8/16/2007 12:55:54 PM | A | CANC |
|
|
Overbooked, no time available for this inspection today.
|
FIR07-00603
| INSP-Sprinkler Rough-in | 8/15/2007 | 8/16/2007 | 8/16/2007 12:55:11 PM | A | CANC |
|
|
Overbooked, no time available for this inspection today.
|
FIR06-00540
| INSP-Sprinkler Rough-in/Hydro | 8/15/2007 | 8/16/2007 | 8/16/2007 12:53:53 PM | A | PART |
|
|
OH inspection for the 4th floor SW quadrant including the kitchen, cafeteria, eating areas, hallway and dining room as marked on approved plans are okay for ceiling cover. Hydrostatic testing for this area to be completed in conjunction with the next pahase of this floor. Also discussed scheduling for the basement seismic upgrades.
|
FIR07-00657
| INSP-Final Inspection | 8/15/2007 | 8/16/2007 | 8/16/2007 12:48:53 PM | A | PASS |
|
|
Fire sprinkler TI work passed final inspection.
|
FIR07-00462
| INSP-Sprinkler Rough-in/Hydro | 8/15/2007 | 8/16/2007 | 8/16/2007 12:47:59 PM | A | PART |
|
|
Fire alarm work completed satisfactory, alarm testing passed, however the preaction riser failed to function properly during testing.
|
FIR07-00474
| INSP-Final Inspection | 8/15/2007 | 8/16/2007 | 8/16/2007 12:46:04 PM | A | FAIL |
|
|
Scope of work is not yet complete, the preaction riser failed to function properly.
|