FIR07-00386
| FIR-Aging Inspection | 8/16/2007 | 8/16/2007 | 8/24/2007 10:35:51 AM | | NR |
|
|
work is in progress
|
BLD06-03127
| FIRE-Final Inspection | 8/15/2007 | 8/16/2007 | 8/17/2007 9:56:19 AM | P | PART |
|
|
life safety passed
|
FIR07-00570
| INSP-Final Inspection | 8/15/2007 | 8/16/2007 | 8/17/2007 9:08:02 AM | P | PASS |
|
|
permit finaled
|
BLD05-03469
| FIRE-Final Inspection | 8/16/2007 | 8/16/2007 | 8/16/2007 3:59:28 PM | P | PART |
|
|
A temporary occupancy was given until the gas meter has been set and the duct smoke detectors can be tested. A condition of the temporary is that the hvac units not be used. I witnessed the power supply to both units being disabled.
|
BLD07-00271
| FIRE-Final Inspection | 8/16/2007 | 8/16/2007 | 8/16/2007 3:56:35 PM | P | CANC |
|
|
This inspection was performed and passed yesterday.
|
BLD07-00288
| FIRE-Final Inspection | 8/15/2007 | 8/16/2007 | 8/16/2007 3:35:50 PM | P | PASS |
|
|
LIfe safety passed.
|
FIR07-00283
| INSP-Final Inspection | 8/16/2007 | 8/16/2007 | 8/16/2007 2:39:12 PM | P | PASS |
|
|
permit finaled
|
BLD06-02647
| FIRE-Final Inspection | 8/15/2007 | 8/16/2007 | 8/16/2007 1:56:29 PM | A | PASS |
|
|
Life safety passed. There is no gas to the hvac units therefore the duct smoke detectors were not tested. They will need to be tested during the tenant buildout which the contractor/builder understands.
|
FIR07-00624
| INSP-Final Inspection | 8/16/2007 | 8/16/2007 | 8/16/2007 12:51:48 PM | P | CANC |
|
|
The sprinkler fitter needs additional time to complete the work. He is going to reschedule for tomorrow. No inspection performed.
|
FIR07-00624
| INSP-Sprinkler Rough-in | 8/16/2007 | 8/16/2007 | 8/16/2007 12:51:18 PM | P | CANC |
|
|
The sprinkler fitter needs additional time to complete the work. He is going to reschedule for tomorrow. No inspection performed.
|
BLD07-00873
| FIRE-Final Inspection | 8/16/2007 | 8/16/2007 | 8/16/2007 12:46:32 PM | A | FAIL |
|
|
There is an access controled egress door at the main exit (big door magnet). This device has not been connected to the fire alarm system. A permit will be required for this work. Also the request to exit button is by the receptionist and exceeds 5' from the door.
|
BLD07-01417
| FIRE-Final Inspection | 8/15/2007 | 8/16/2007 | 8/16/2007 12:42:37 PM | A | FAIL |
|
|
The existing exit sign for the corridor exit did not switch to battery backup and will need repaired. All other items appeared ok.
|
BLD07-00598
| FIRE-Final Inspection | 8/16/2007 | 8/16/2007 | 8/16/2007 11:44:51 AM | P | FAIL |
|
|
No approved plans on site and the contractor was not answering his phone.
|
FIR05-00536
| INSP-Sprinkler Rough-in/Hydro | 8/15/2007 | 8/16/2007 | 8/16/2007 11:24:06 AM | A | PASS |
|
|
Third floor hydro test passed
|
BLD07-00836
| FIRE-Final Inspection | 8/15/2007 | 8/16/2007 | 8/16/2007 11:23:35 AM | A | FAIL |
|
|
Repair the exit sign over the main door and provide the double door as discussed so that hardware can be verified.
|
FIR07-00646
| INSP-Final Inspection | 8/15/2007 | 8/16/2007 | 8/16/2007 9:51:06 AM | A | PASS |
|
|
Permit is finaled
|
BLD07-00491
| FIRE-Final Inspection | 8/16/2007 | 8/16/2007 | 8/16/2007 9:07:34 AM | P | FAIL |
|
|
Per the approved plans there is supposed to be a fire alarm permit for the new duct detector. Per mike timmerman there isn't any applied for yet and per the custodian the permanant doors are not installed yet.
|
FIR07-00642
| INSP-Final Inspection | 8/15/2007 | 8/16/2007 | 8/16/2007 8:43:15 AM | A | FAIL |
|
|
This inspection was just for the electronics area and for part of the womens clothing department. See the city approved plans for the exact locations.
|