FIR11-00159
| INSP-Final Inspection | 8/16/2011 | 8/16/2011 | 8/16/2011 3:50:40 PM | P | FAIL |
|
|
All correction items have been addressed. Project can be finaled when the fire alarm interconnections have been tested.
|
BLD11-01804
| FIRE-Final Inspection | 8/16/2011 | 8/16/2011 | 8/16/2011 3:48:51 PM | P | PASS |
|
|
life safety passed
|
FIR11-00400
| INSP-Final Inspection | 8/16/2011 | 8/16/2011 | 8/16/2011 3:47:55 PM | P | PASS |
|
|
Permit finaled. Ground fault repaired.
|
FIR11-00400
| INSP-Final Inspection | 8/16/2011 | 8/16/2011 | 8/16/2011 3:46:42 PM | P | FAIL |
|
|
The interior a/v's did not work due to a ground fault.
|
FIR11-00167
| INSP-Final Inspection | 8/15/2011 | 8/16/2011 | 8/16/2011 2:11:28 PM | P | PASS |
|
|
Permit finaled. The forward flush passed.
|
FIR11-00321
| INSP-Alarm Testing | 8/15/2011 | 8/16/2011 | 8/16/2011 1:53:50 PM | P | PASS |
|
|
Permit finaled
|
FIR11-00402
| INSP-Final Inspection | 8/16/2011 | 8/16/2011 | 8/16/2011 12:46:42 PM | P | FAIL |
|
|
There is apparently a problem with the tamper switch circuit. They will require retesting prior to a sign off. The flow switches and smoke detector over the facp functioned and reported.
|
FIR11-00299
| INSP-Sprinkler Rough-in | 8/15/2011 | 8/16/2011 | 8/16/2011 12:44:32 PM | A | PASS |
|
|
The sprinkler rough-in passed. The temporary items have been completed except for a hydro test and a sprinkler head in the temporary riser "dog house".
|
BLD11-01069
| FIRE-Final Inspection | 8/15/2011 | 8/16/2011 | 8/16/2011 9:42:50 AM | A | FAIL |
|
|
Provide sprinkler protection in the two rooms that are located within the sprinklered portion of the building. One room is being used for storage the other is a telephone room. All other life safety items are ok.
|
BLD11-01411
| FIRE-Final Inspection | 8/15/2011 | 8/16/2011 | 8/16/2011 8:18:14 AM | A | PASS |
|
|
life safety passed
|