FIR12-00237
| INSP-Alarm Testing | 8/15/2012 | 8/15/2012 | | P | |
|
|
Please call 30 min prior to arrival Phone #: ###-#### >> Inspection requested via web by Jeff Walton
|
BLD12-01557
| FIRE-Final Inspection | 8/15/2012 | 8/16/2012 | 8/16/2012 5:05:18 PM | P | PASS |
|
|
Fire life safety inspection completed acceptable.
|
FIR12-00415
| INSP-Final Inspection | 8/16/2012 | 8/16/2012 | 8/16/2012 5:04:05 PM | P | PASS |
|
|
Fire alarm permit finaled.
|
FIR12-00415
| INSP-Alarm Testing | 8/15/2012 | 8/16/2012 | 8/16/2012 5:03:38 PM | P | PASS |
|
|
Fire alarm modifications passed functional test.
|
BLD12-01200
| FIRE-Final Inspection | 8/16/2012 | 8/16/2012 | 8/16/2012 3:13:24 PM | P | FAIL |
|
|
Missing egress lighting per IFC 1006.1.
|
FIR12-00354
| INSP-Sprinkler Rough-in | 8/16/2012 | 8/16/2012 | 8/16/2012 3:11:49 PM | P | PART |
|
|
Overhead work approved for cover with the exception of the west stair landing- provide a drop ceiling or relocate the pendent sprinkler to an upright position at the deck. Also need to complete a hydrostatic test per review comments (ref. NFPA 25).
|
FIR12-00355
| INSP-Final Inspection | 8/16/2012 | 8/16/2012 | 8/16/2012 3:07:12 PM | P | NR |
|
|
Missing permit documents on site.
|
FIR12-00314
| INSP-Sprinkler Rough-in | 8/15/2012 | 8/16/2012 | 8/16/2012 3:03:00 PM | A | PART |
|
|
Overhead work at the new restrooms okay for cover- see dated plan annotations.
|