BLD16-02487
| FIRE-Final Inspection | 8/16/2016 | 8/16/2016 | 8/16/2016 2:19:59 PM | P | CANC |
|
|
Request was for a fire conference, not a final fire inspection. Fire conference complete.
|
BLD15-02368
| FIRE-Final Inspection | 8/15/2016 | 8/16/2016 | 8/16/2016 1:57:21 PM | P | FAIL |
|
|
Fire sprinkler heads still masked off for painting, heads need to be uncovered and escutcheons need to be installed, numerous heads missing escutcheons throught level 9. Fire alarm inspection is complete and fire extinguishers are in place with current inspection tags.
|
FIR16-00265
| INSP-Sprinkler Rough-in | 8/16/2016 | 8/16/2016 | 8/16/2016 1:54:44 PM | P | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping located above hardlids in VRT complete, overhead fire sprinkler piping above hardlids in VRT approved for cover.
|
FIR15-00727
| INSP-Sprinkler Rough-in/Hydro | 8/16/2016 | 8/16/2016 | 8/16/2016 1:54:07 PM | P | CANC |
|
|
Hydrostatic test will be reschedule for later date.
|
FIR16-00215
| INSP-Final Inspection | 8/10/2016 | 8/16/2016 | 8/16/2016 8:51:25 AM | A | PASS |
|
|
Final fire alarm inspection passed/complete
|