FIR18-00400
| INSP-Sprinkler Rough-in | 8/15/2018 | 8/16/2018 | 8/16/2018 2:18:29 PM | P | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.
Tom Phone #: ###-####
|
BLD18-02553
| FIRE-Final Inspection | 8/16/2018 | 8/16/2018 | 8/16/2018 2:17:30 PM | P | PART |
|
|
Racking that is 17 foot tall will require a resubmittal, racks can be used up to the 12 foot mark per city approved drawings. After plan modification is made a re-inspection will be required to verify installation matches city approved drawings.
pallet racking Phone #: ###-#### Inspection requested via web by Jeff Higgins
|
BLD18-02099
| FIRE-Conference | 8/15/2018 | 8/16/2018 | 8/16/2018 10:38:35 AM | A | DONE |
|
|
Fire conference complete, new kitchen cooking equipment is being installed under kitchen hoods, a FIR permit will be required for modifications that will need to be made to existing hood system.
Look at code compliance of kitchen hoods Phone #: ###-#### Inspection requested via web by Steve Jones
|
FIR18-00267
| INSP-Sprinkler Rough-in/Hydro | 8/14/2018 | 8/16/2018 | 8/16/2018 10:05:28 AM | A | PASS |
|
|
24 hour air test complete for dry systems in fire pump room.
JUSTIN IS OUR CONTACT THIS IS TO FINISH THE (3) 24 HOUR AIR TEST FOR THE DRY SYSTEMS IN THE PARKING LEVELS Phone #: ###-#### Inspection requested via web by Brad Bettencourt
|
FIR18-00117
| INSP-Supply line flush | 8/14/2018 | 8/16/2018 | 8/16/2018 10:04:39 AM | A | DONE |
|
|
Underground main line flush complete.
THIS IS A UNDERGROUND FLUSH AT 10:00 AM WITH SUEZ WATER JUSTIN IS OUR CONTACT Phone #: ###-#### Inspection requested via web by Brad Bettencourt
|
FIR18-00602
| INSP-Sprinkler Rough-in | 8/16/2018 | 8/16/2018 | 8/16/2018 9:32:06 AM | A | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.
RANDY COURTRIGHT Phone #: ###-#### Inspection requested via web by Brodie Stenquist
|
FIR18-00153
| INSP-Sprinkler Rough-in/Hydro | 8/16/2018 | 8/16/2018 | 8/16/2018 8:57:04 AM | A | PASS |
|
|
Hydrostatic test for overhead fire sprinkler piping witnessed at static pressure, no pressure loss observed at riser provided gauge.
|
FIR18-00153
| INSP-Sprinkler Rough-in | 8/15/2018 | 8/16/2018 | 8/16/2018 8:54:53 AM | A | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping/tenting complete, approved for cover.
Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00606
| INSP-Sprinkler Rough-in | 8/14/2018 | 8/16/2018 | 8/16/2018 8:13:51 AM | A | PASS |
|
|
Rough to cover ispection for overhead fire sprinkler piping in area of work complete, approved for cover.
Rough to cover Phone #: ###-#### Inspection requested via web by Stan Beus
|