Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-02833 Final8/15/20198/16/20198/16/2019 2:45:18 PMPPASS
Call Journeyman, Barry Spencer, with any timeframe/questions. ###-#### Phone #: ###-#### Inspection requested via web by Rob Maes....
outlets either fished down walls or surface mount wiring...in-use covers and GFCI protection requirements met...ok to final
ELE19-02587 Final8/15/20198/16/20198/16/2019 2:43:29 PMPPASS
Call journeyman, Barry Spencer, with any questions.timeframe. ###-#### Phone #: ###-#### Inspection requested via web by Rob Maes...
labelling, disconnect, and OCPD ok
ELE19-03068 Temporary Service8/16/20198/16/20198/16/2019 2:11:57 PMPPASS
This Will Be All Ready For Inspection For Ya Thanks Phone #: ###-#### Inspection requested via web by jason shifflett...t/s u/g new ok
ELE19-02898 Final8/16/20198/16/20198/16/2019 1:55:44 PMPPASS
Phone #: ###-#### Inspection requested via web by Virginia Jesop...
labelling, disconnect, and OCPD
ELE19-02898 Electrical Rough-In8/13/20198/16/20198/16/2019 1:54:47 PMAPASS
Phone #: ###-#### Inspection requested via web by Virginia Jesop...
UL listing and bonding verified
ELE18-02136 Final8/15/20198/16/20198/16/2019 12:32:03 PMPPASS
Electrical final for the RTU
Jason is the contact. If you call and give Jason a one hour notice than he will meet you there. Phone #: ###-#### Inspection requested via web by Deb Ipsen..
disconnects and labelling for rooftop units and ground mini spilts ok...GFCI service recps verified...ok to final
ELE19-02945 Electrical Rough-In8/16/20198/16/20198/16/2019 11:45:52 AMPPASS
wall cover Phone #: ###-#### Inspection requested via web by David Feller...
rough in wall cover only ok
ELE19-02883 Final8/15/20198/16/20198/16/2019 11:32:58 AMPPASS
Contact Journeyman, Barry Spencer, with any questions ###-#### Phone #: ###-#### Inspection requested via web by Rob Maes...
labelling, disconnect,and OCPD ok
ELE19-02883 Electrical Rough-In8/15/20198/16/20198/16/2019 11:32:08 AMAPASS
Contact, Journeyman, Barry Spencer with any questions or timeframe. ###-#### Phone #: ###-#### Inspection requested via web by Rob Maes...UL listed equipment
ELE19-03006 Final8/15/20198/16/20198/16/2019 11:31:38 AMAPASS
Contact Barry Spencer, with any questions or timeframe. Phone #: ###-#### Inspection requested via web by Rob Maes...ok to final
ELE19-03065 Final8/15/20198/16/20198/16/2019 10:55:08 AMANH
replaced 30 amp breaker with 25 amp breaker for A/C. It is ready. Thank You. Phone #: ###-#### Inspection requested via web by Kelly Felin...
no one home...notification left on door
ELE19-01750 Final8/16/20198/16/20198/16/2019 10:46:02 AMAPASS
key is in back behind AC inside low voltage box Phone #: ###-#### Inspection requested via web by cal crosby...corrections made ok to final
ELE19-02908 Final8/16/20198/16/20198/16/2019 10:28:34 AMAPASS
Phone #: ###-#### Inspection requested via web by Virginia Jesop....
Labelling, disconnect, and OCPD...ok to final
ELE19-02908 Electrical Rough-In8/13/20198/16/20198/16/2019 10:28:00 AMAPASS
Phone #: ###-#### Inspection requested via web by Virginia Jesop...UL listing verified
ELE19-03025 Electrical Rough-In8/15/20198/16/20198/16/2019 9:43:44 AMAPASS
Corrections made Phone #: ###-#### Inspection requested via web by David Green...ok
ELE19-01316 Final8/16/20198/16/20198/16/2019 9:28:00 AMAPART
Last 6 units south Phone #: ###-#### Inspection requested via web by Kevin Burke...units 100, 102, 201, 202 301, 302...ok to final
exterior remaining
ELE18-02397 Rough-In Permanent Service8/15/20198/16/20198/16/2019 8:26:38 AMACANC
As early as possible Phone #: 5039302430 >> Inspection requested via mobile web by Timothy Frey...inspection was for pipe depth feeding service to building...informed homeowner that needs to be done by ID Power
ELE19-02026 Electrical Rough-In8/15/20198/16/20198/16/2019 8:16:12 AMACANC
I do have a junction box installed above the ceiling and I''ll send Tom pictures. Phone #: ###-#### Inspection requested via web by John Johnson...canceled by calling 8:14am 8/16/19
ELE18-03645 Electrical Rough-In8/15/20198/16/20198/16/2019 8:03:05 AMAPASS
Todd Phone# ###-####
moved from previous day...agreed to be there at 7:45...first inspection...Tom...wiring ok to cover...early morning works best for future inspections...soffit outlets complete and verified GFCI protection...lighting and fan left to verify
ELE15-03283 ELE-Aging Inspection8/16/20198/16/20198/16/2019 7:12:24 AM FAIL
contractor making no attempt
ELE19-02676 Permanent Service8/15/20198/16/20198/15/2019 12:55:05 PMACANC
Phone #: ###-#### >> Inspection requested via web by jamie berg Inspection cancelled from web by: jamie berg