Inspections for the day of: Friday, August 16, 2019.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00524 INSP-Sprinkler Rough-in8/16/20198/16/20198/16/2019 4:25:14 PMPPASS
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.

Adam Phone #: ###-####
FIR19-00426 INSP-Sprinkler Rough-in8/16/20198/16/20198/16/2019 4:24:39 PMPPASS
Previously noted items for rough in have been corrected, cover is approved.

FIR19-00426 INSP-Sprinkler Rough-in/Hydro8/15/20198/16/20198/16/2019 4:23:41 PMPDONE
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed.

Contact Kieth Orahood 208-629--9953 30 min Prior to Hydro Insp start please. He''s requesting an Early PM insp if at all possible.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
BLD19-03064 FIRE-Final Inspection8/16/20198/16/20198/16/2019 2:14:41 PMPPASS
No fire sprinklers, no fire alarms, fire extinguisher will be relocated to discussed location. Final life fire safety inspection complete.

Cndy Phone #: ###-####
FIR19-00469 INSP-Final Inspection8/16/20198/16/20198/16/2019 1:48:34 PMPPASS
Final fire sprinkler inspection for scope of work complete.

Contact is Chris Phone #: ###-#### Inspection requested via web by Chris Green
FIR19-00399 INSP-Final Inspection8/9/20198/16/20198/16/2019 1:46:14 PMPPASS
Final fire sprinkler inspection for area of work complete.

Phone #: ###-#### Inspection requested via web by Connie Danes
FIR19-00399 INSP-Sprinkler Rough-in8/16/20198/16/20198/16/2019 1:45:44 PMPPASS
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.
BLD19-00290 FIRE-Final Inspection8/15/20198/16/20198/16/2019 1:03:22 PMPCANC
Phone #: ###-#### >> Inspection requested via web by Brian Wilson Inspection cancelled from web by: Brian Wilson
BLD19-02252 FIRE-Final Inspection8/15/20198/16/20198/16/2019 11:27:35 AMAPASS
Fire sprinkler modifications, are complete, no fire alarm modifications, fire extinguisher will be mounted in discussed location. Final life fire safety inspection for area of work complete.

Don ###-####
FIR18-00886 INSP-Final Inspection8/15/20198/16/20198/16/2019 10:49:54 AMPPART
Previously noted items for phase 2 complete, final fire sprinkler inspewction for phase 2 complete.

Contact hunter Anderson ###-#### 30 Min prior to Final Insp Phase 2 start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
FIR19-00379 INSP-Alarm Testing8/15/20198/16/20198/16/2019 10:45:56 AMAPART
Previously noted items for phase 2 complete, final fire alarm inspection for phase 2 complete.

Contact is Rob. Phone #: ###-#### Inspection requested via web by Morgan Ahten
FIR19-00306 INSP-Sprinkler Rough-in8/15/20198/16/20198/16/2019 9:20:17 AMAPART
Partial rough to cover inspection for overhead fire sprinkler piping in area of work complete, notated city approved drawings on site with pink hughlighter areas approved for cover.

Rough in for Phase 1. Please highlight phase 1 when finished. Tom M. Has prints for Straightline Phone #: ###-#### Inspection requested via web by Sam Ball
FIR18-00572 INSP-Final Inspection8/15/20198/16/20198/16/2019 12:00:00 AMAPASS
Brandon or ###-#### Kristen Phone #: ###-####
All worked properly. Tested with Damien.
FIR19-00279 INSP-Final Inspection8/15/20198/16/20198/15/2019 5:46:41 PMACANC
Inspecting Technician: Ray McQueen Phone #: ###-#### >> Inspection requested via web by Rose Peterson Inspection cancelled from web by: Rose Peterson
FIR18-00678 INSP-Final Inspection8/9/20198/16/20198/15/2019 3:16:33 PMACANC
Phone #: ###-#### >> Inspection requested via web by Connie Danes Inspection cancelled from web by: Connie Danes