Inspections for the day of: Friday, August 16, 2019.
Number of inspections: 31
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Reynolds
TitleMEC INSPECTOR
Phone #208-803-2395
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC19-01499 Final8/15/20198/16/20198/16/2019 4:04:12 PMPPASS
TENANT LYNN WILL BE HOME BUT DOESN''T HAVE A PHONE. CONTACT # IS FOR HOUSE AGENT ONLY. Phone #: ###-#### Inspection requested via web by SOPHIA FLEMING
- final ok
MEC19-03584 Final8/15/20198/16/20198/16/2019 3:44:28 PMPFAIL
Please call Maddie on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks
- furnace flue needs 1" clearances to new flex ducting
- need to see co detectors installed near bedrooms
MEC19-00785 Final8/15/20198/16/20198/16/2019 3:26:34 PMPPASS
Phone #: ###-#### Inspection requested via web by Oleg Chervak
- final ok
- signed occ card BLD H
MEC19-03548 Final8/12/20198/16/20198/16/2019 2:49:17 PMPFAIL
Field super: Chad Robertson Phone #: ###-#### Inspection requested via web by Lisa Whitney
- furnace ac coil co ok
- ductless split ok
- need to see an electrical permit pulled for ductless split system
MEC19-03535 Final8/9/20198/16/20198/16/2019 2:22:41 PMPPASS
INSTALLER DAVID ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt
- furnace ac coil co ok
MEC19-03500 Final8/12/20198/16/20198/16/2019 1:25:50 PMPPASS
Homeowner Cassie Germano ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette
- furnace ac coil co ok
MEC19-02964 Rough-in8/15/20198/16/20198/16/2019 12:05:25 PMAPASS
rough-final for a temporary occupancy. All exhaust fans are in, expect kitchen hoods. dryer vents are in, and GDRS are in. Gas lines are NOT done and gas lines has been pushed back GC doesnt need them right now. Phone #: ###-#### Inspection requested via web by adrian manzo
- R/I ok
MEC19-02964 Final8/16/20198/16/20198/16/2019 12:04:58 PMAPART
rough-final for a temporary occupancy. All exhaust fans are in, expect kitchen hoods. dryer vents are in, and GDRS are in. Gas lines are NOT done and gas lines has been pushed back GC doesnt need them right now. Phone #: ###-#### Inspection requested via web by adrian manzo
- partial final ok
- signed temp occ
MEC19-03644 Rough-in8/16/20198/16/20198/16/2019 11:47:54 AMANH
I have my dryer vent roughed in and would like to proceed with installing the floor so I thought it would be a good time to look at that part of the job. If there are any issues please call me at 208.941.3408 Phone #: ###-#### Inspection requested via web by JEFFREY DAVIS
- no access to home left notice on front door
MEC19-03659 Final8/15/20198/16/20198/16/2019 11:34:44 AMAPASS
PLEASE CALL TENANT JAMES @ # LISTED WHEN EN ROUTE ; COME BETWEEN 8:30 A.M. - 9:30 A.M. IF POSSIBLE. Phone #: ###-#### Inspection requested via web by SOPHIA FLEMING
- A/C coil co ok
MEC19-03535 Pressure Test8/9/20198/16/20198/16/2019 11:25:11 AMAPASS
INSTALLER DAVID ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt
- 20lb gas pressure test ok
MEC19-03362 Final8/14/20198/16/20198/16/2019 11:13:05 AMAPASS
Please inspect in the late AM and call the customer when on way: Barbara ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks
-final ok
MEC19-03672 Final8/15/20198/16/20198/16/2019 10:14:53 AMAPASS
call Kim Phone #: ###-#### Inspection requested via web by Kim Lithander
- A/C coil co ok
MEC19-03654 Final8/15/20198/16/20198/16/2019 9:58:01 AMAPASS
PLEASE CALL TENANT KENT WHEN 30 MINS IN ROUTE Phone #: ###-#### Inspection requested via web by Rick Montgomery
- furnace ac coil co ok
MEC19-03632 Final8/14/20198/16/20198/16/2019 9:38:33 AMAFAIL
Renter will be home all day...
Furnace and gas line to range are in basement Phone #: ###-#### Inspection requested via web by Rick Jones
- 20lb gas pressure test ok
- furnace vent in basment needs 6' clearances to combustibles or changed to b vent
MEC19-02654 Final8/15/20198/16/20198/16/2019 9:25:39 AMAPASS
I sent you pics 8/14 to pass Phone #: ###-#### Inspection requested via web by Mary LaFayette
- final ok
MEC19-03658 Rough-in8/15/20198/16/20198/16/2019 9:18:02 AMAPASS
PLEASE CALL CONTRACTOR NATE WHEN EN ROUTE Phone #: ###-#### Inspection requested via web by SOPHIA FLEMING
- R/I ok
- need to see ducting in the floor under cabinets ducted out by final
- need to add 2 exhaust fans to permit
- check range venting
MEC19-03546 Rough-in8/15/20198/16/20198/16/2019 8:48:53 AMACANC
Phone #: ###-#### >> Inspection requested via web by Konrad Swartz Inspection cancelled from web by: Konrad Swartz
MEC19-03661 Rough-in8/16/20198/16/20198/16/2019 8:44:44 AMAPART
Project is open in back yard Phone #: ###-#### Inspection requested via web by Angie Thome
- supply ducting ok
- exhasut fan ducting ok
- it looks like some b vent is going to be installed within this project. Will want to see new venting installed for R/I inspection
- Talked with the builder this morning about the bvent being installed. Sounds like the water heater is going to be changed to gas. The plumber with be running a new gas line to the water heater and a gas range. The city will need to see a permit pulled by other before giving a final on this mechanical permit.
MEC19-02061 Final8/15/20198/16/20198/16/2019 8:35:07 AMAPASS
Code 5050 Phone #: ###-#### Inspection requested via web by Teresa Costello
- final ok
MEC19-02062 Final8/15/20198/16/20198/16/2019 8:34:53 AMAPASS
Code 5050 Phone #: ###-#### Inspection requested via web by Teresa Costello
- final ok
MEC19-01074 Final8/15/20198/16/20198/16/2019 8:22:48 AMAPASS
Code 5050
Phone #: ###-#### Inspection requested via web by Teresa Costello
- final ok
MEC19-01073 Final8/15/20198/16/20198/16/2019 8:22:34 AMAPASS
Code 5050 Phone #: ###-#### Inspection requested via web by Teresa Costello
- final ok
MEC19-03661 Final8/15/20198/16/20198/16/2019 8:12:51 AMACANC
Project is open in back yard Phone #: ###-#### Inspection requested via web by Angie Thome
- I changed this inspection to a R/I and partialed it
- it looks like b vent flueing is being installed somewhere on this project and will need to see it for R/I
MEC19-00052 Mec-Aging Inspection8/16/20198/16/20198/16/2019 7:51:57 AM FAIL
This permit has not been active since being issued on 1/4/19. If work is finished schedule inspection with homeowner. Permit will expire at next aging inspection if not active
MEC18-04803 Mec-Aging Inspection8/16/20198/16/20198/16/2019 7:47:44 AM PASS
permit expired not active
MEC18-04803 DOC - Permit Expired8/16/20198/16/20198/16/2019 7:47:27 AMAPASS
doc permit expired ok not active
MEC19-01073 Final8/15/20198/16/20198/15/2019 2:51:55 PMACANC
Phone #: ###-#### >> Inspection requested via web by Teresa Costello Inspection cancelled from web by: Teresa Costello
MEC19-01074 Final8/15/20198/16/20198/15/2019 2:51:18 PMACANC
Phone #: ###-#### >> Inspection requested via web by Teresa Costello Inspection cancelled from web by: Teresa Costello
MEC19-02061 Final8/15/20198/16/20198/15/2019 2:50:53 PMACANC
Phone #: ###-#### >> Inspection requested via web by Teresa Costello Inspection cancelled from web by: Teresa Costello
MEC19-02062 Final8/15/20198/16/20198/15/2019 2:50:21 PMACANC
Phone #: ###-#### >> Inspection requested via web by Teresa Costello Inspection cancelled from web by: Teresa Costello