BLD03-01845
| FIRE-Final Inspection | 8/11/2005 | 8/11/2005 | | P | |
|
|
cane up on aging.jstorey
|
FIR05-00155
| INSP-Sprinkler Rough-in | 8/17/2005 | 8/17/2005 | 8/18/2005 1:26:20 PM | P | FAIL |
|
|
Hanger in nursery room 127 needs retaining strap attatched, head in corridor outside room 127 needs a hanger installed on the armover. All remaining areas are okay to cover.
|
BLD05-01469
| FIRE-Final Inspection | 8/17/2005 | 8/17/2005 | 8/17/2005 3:13:20 PM | P | PASS |
|
|
Fire life safety is satisfactory for final.
|
MIS05-00118
| FIR-Final | 8/17/2005 | 8/17/2005 | 8/17/2005 2:02:05 PM | P | PASS |
|
|
Life safety passed, temporary occupancy approved by the structural inspector pending approved hardware at main entry/exit.
|
FIR05-00436
| INSP-Final Inspection | 8/16/2005 | 8/17/2005 | 8/17/2005 10:44:46 AM | A | FAIL |
|
|
Need to coordinate trip test for new dry valve functionality verification.
|
BLD05-00573
| FIRE-Final Inspection | 8/16/2005 | 8/17/2005 | 8/17/2005 10:04:45 AM | A | PASS |
|
|
Life safety passed inspection.
|
FIR05-00505
| INSP-Final Inspection | 8/17/2005 | 8/17/2005 | 8/17/2005 12:00:00 AM | A | PASS |
|
|
Fire sprinkler permit work passed inspection.
|
FIR05-00266
| INSP-Sprinkler Rough-in | 8/17/2005 | 8/17/2005 | 8/17/2005 12:00:00 AM | A | PART |
|
|
Underground fire supply line between the restaurant and the boarding house is acceptable to cover with the sleeve installed per Bill Alexander.
|
FIR05-00431
| INSP-Final Inspection | 8/17/2005 | 8/17/2005 | 8/17/2005 12:00:00 AM | P | PASS |
|
|
Fire sprinkler finaled.
|
FIR05-00384
| INSP-Final Inspection | 8/17/2005 | 8/17/2005 | 8/17/2005 12:00:00 AM | P | PASS |
|
|
Permit finaled.
|
FIR05-00266
| INSP-Sprinkler Rough-in | 8/16/2005 | 8/17/2005 | | A | |
|
|
###-#### - bruce Note: after morning 9:00 ish
|