Inspections for the day of: Wednesday, August 17, 2005.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD04-02676 FIRE-Final Inspection8/16/20058/17/20058/17/2005 4:21:45 PMACANC
fred; Phone #: ###-####
No inspection performed. I performed inspection for BLD05-00574.
FIR05-00427 INSP-Final Inspection8/16/20058/17/20058/17/2005 3:50:56 PMPFAIL
Of the two systems the suppression system over the griddle operated correctly. The suppression sytem over the fryers operated but the gas valve did not operate. Need to retest this and the manual pull as well as get documents for final.
FIR01-00625 FIR-Aging Inspection8/17/20058/17/20058/17/2005 3:46:35 PM PASS
permit finaled
FIR05-00217 INSP-Final Inspection8/17/20058/17/20058/17/2005 3:29:10 PMPFAIL
Forward flush passed but need to certify the backflow preventor, provide verification of the spacing in the conference room and the additional dry pendants with bill as previously requested. Verify that the valve for the ball drip in the pit is open
FIR05-00189 INSP-Final Inspection8/17/20058/17/20058/17/2005 3:27:28 PMAFAIL
Relocate manual pull down 2". Provide horn only. Provide signage on riser room door. Provide verification of all points sent in. Provide map at facp.
BLD04-02934 FIRE-Sprinkler Rough-in8/16/20058/17/20058/17/2005 1:15:22 PMPCANC
don ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
FIR05-00395 INSP-Final Inspection8/17/20058/17/20058/17/2005 11:24:59 AMPPASS
Fire alarm finaled
BLD05-01484 FIRE-Final Inspection8/16/20058/17/20058/17/2005 10:50:02 AMAFAIL
Inspection was for insulation being re-attached to the deck since it was previously laying on the sprinkler piping. The insulation over the sales floor has been repaired but over the restrooms and offices there are still problems. Ceiling is ok to be installed but office area/restroom will need to be spot checked at the building final.
FIR05-00356 INSP-Alarm Testing8/15/20058/17/20058/17/2005 10:17:45 AMAFAIL
Resubmit plans showing the PIV. Device has been tested and comes in as point 20. Update map with the PIV and hilight the initiating devices for easier locating. Provide signage on the door to the fire alarm control panel.
BLD05-01220 FIRE-Final Inspection8/16/20058/17/20058/17/2005 10:15:55 AMAPASS
Life safety finaled
FIR01-00624 FIR-Aging Inspection8/17/20058/17/20058/17/2005 7:44:35 AM PASS
Permit finaled
FIR01-00624 FIR-Aging Inspection8/17/20058/17/20058/17/2005 7:44:31 AMPPASS
Permit finaled
FIR04-00542 INSP-Final Inspection8/11/20058/17/20058/17/2005 7:20:28 AMAPASS
Permit finaled
BLD05-00574 FIRE-Final Inspection8/17/20058/17/20058/17/2005 12:00:00 AMPFAIL
Provide knox key box per note #9. Provide painting or signage per note #11. Provide exit discharge lighting per note #5. Provide approved door hardware per notes #14 and #15. Repair the fire alarm panel and provide the requirements of note #24. Provide clear path of travel, non locking hardware, through doors with exit signs or meet with plan review to possibley remove exit signs.