Inspections for the day of: Thursday, August 17, 2006.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-01801 ELE-Aging Inspection8/17/20068/17/20068/18/2006 7:37:15 AM PART
wsuc
ELE05-04325 Electrical Rough-In8/17/20068/17/20068/17/2006 4:14:10 PMPNR
jason; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley
300.4 nail plates and 11/4", 330.30 (B) strap mc within 12" boxes, 310.15B deration for mc, or spacing for cables
ELE06-01970 Final8/16/20068/17/20068/17/2006 3:17:02 PMPFAIL
ron; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley see added r/i note only r/i inspections ever called in are for concrete encased electrode and u/g
ELE06-01970 Electrical Rough-In8/17/20068/17/20068/17/2006 3:15:45 PMPFAIL
ron; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley corr. called
r/i inspection added 312.5 connector for GEC new building, old small building B C C no violations retained, 200.6 shall have required color for neutral, shall not ID 6 or smaller, 250.32 shall prvide made electrode, grd or bond water system if there, 225.31,32,36, 110.3(B), 408.34(A) shall provide service suitible for service equip as manufactures instructions state, note needs main breaker because it is not a power panelboard per manufactures instruction it is a lighting panelboard
ELE06-03008 Electrical Rough-In8/16/20068/17/20068/17/2006 2:27:30 PMPNH
Dan; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt notice posted called
ELE06-03066 Temporary Service8/17/20068/17/20068/17/2006 1:45:32 PMPPASS
Internet Inspection Request from: Rowdy Monroe t/s u/g new ok
ELE06-03039 Electrical Rough-In8/17/20068/17/20068/17/2006 1:19:57 PMPPART
PAUL UNDERGROUND AND CEILING COVER; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy
u/g ok only corr. for ceiling, 300.11 support wires shall be from grid to structure, 330.30
(B)&(D2), 210.62 added show window outlet
ELE06-03065 Permanent Service8/17/20068/17/20068/17/2006 12:14:53 PMPFAIL
Jack; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt corr called 250.52(A)(1)or 104(A)(1) grd or bond water sized table 250.66, 250.64(C) shall not splice GEC
ELE06-00711 Electrical Rough-In8/16/20068/17/20068/17/2006 10:47:09 AMAPART
Scheduled by a contractor via Hello! on 8/16/2006 at 3:38:42 PM. Contact: ###-####. called left message 2nd floor anop
ELE06-02994 Electrical Rough-In8/17/20068/17/20068/17/2006 9:19:05 AMAPART
ug conduit; all trenches get 8" of gravel and 6" of concrete on top of them; Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack 3 pole lights ok
ELE06-03039 Electrical Rough-In8/16/20068/17/20068/17/2006 9:15:03 AMPCANC
underground Internet Inspection Request from: Tyler Bowen Inspection cancelled from web by: Sean DeLacy
ELE06-03050 Final8/16/20068/17/20068/17/2006 8:37:24 AMAPASS
Call Jerry @ ###-#### 10 minutes before inspecting. Work performed by Tom Wonacott.; Phone #: ###-#### Internet Inspection Request from: Matt Santacruz
ELE06-03059 Permanent Service8/16/20068/17/20068/17/2006 8:23:18 AMAPASS
panel was pulled off in storm. We put a mast head and put panel back on. My cell is ###-####. thanks Randy; Phone #: ###-#### Internet Inspection Request from: Randy Fletcher p/s o/h rec. ok
ELE06-03059 Final8/17/20068/17/20068/17/2006 8:22:53 AMAPASS
panel was pulled off in storm. We put a mast head and put panel back on. My cell is ###-####. thanks Randy; Phone #: ###-#### Internet Inspection Request from: Randy Fletcher
ELE06-03051 Electrical Rough-In8/16/20068/17/20068/17/2006 12:00:00 AMACANC
cancel per randy vail//blb DAVE OWEN - PLEASE CALL & HE WILL MEET @ JOBSITE; Phone #: ###-#### Internet Inspection Request from: Randy Vail