ELE06-01801
| ELE-Aging Inspection | 8/17/2006 | 8/17/2006 | 8/18/2006 7:37:15 AM | | PART |
|
|
wsuc
|
ELE05-04325
| Electrical Rough-In | 8/17/2006 | 8/17/2006 | 8/17/2006 4:14:10 PM | P | NR |
|
|
jason; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley 300.4 nail plates and 11/4", 330.30 (B) strap mc within 12" boxes, 310.15B deration for mc, or spacing for cables
|
ELE06-01970
| Final | 8/16/2006 | 8/17/2006 | 8/17/2006 3:17:02 PM | P | FAIL |
|
|
ron; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley see added r/i note only r/i inspections ever called in are for concrete encased electrode and u/g
|
ELE06-01970
| Electrical Rough-In | 8/17/2006 | 8/17/2006 | 8/17/2006 3:15:45 PM | P | FAIL |
|
|
ron; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley corr. called r/i inspection added 312.5 connector for GEC new building, old small building B C C no violations retained, 200.6 shall have required color for neutral, shall not ID 6 or smaller, 250.32 shall prvide made electrode, grd or bond water system if there, 225.31,32,36, 110.3(B), 408.34(A) shall provide service suitible for service equip as manufactures instructions state, note needs main breaker because it is not a power panelboard per manufactures instruction it is a lighting panelboard
|
ELE06-03008
| Electrical Rough-In | 8/16/2006 | 8/17/2006 | 8/17/2006 2:27:30 PM | P | NH |
|
|
Dan; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt notice posted called
|
ELE06-03066
| Temporary Service | 8/17/2006 | 8/17/2006 | 8/17/2006 1:45:32 PM | P | PASS |
|
|
Internet Inspection Request from: Rowdy Monroe t/s u/g new ok
|
ELE06-03039
| Electrical Rough-In | 8/17/2006 | 8/17/2006 | 8/17/2006 1:19:57 PM | P | PART |
|
|
PAUL UNDERGROUND AND CEILING COVER; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy u/g ok only corr. for ceiling, 300.11 support wires shall be from grid to structure, 330.30 (B)&(D2), 210.62 added show window outlet
|
ELE06-03065
| Permanent Service | 8/17/2006 | 8/17/2006 | 8/17/2006 12:14:53 PM | P | FAIL |
|
|
Jack; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt corr called 250.52(A)(1)or 104(A)(1) grd or bond water sized table 250.66, 250.64(C) shall not splice GEC
|
ELE06-00711
| Electrical Rough-In | 8/16/2006 | 8/17/2006 | 8/17/2006 10:47:09 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 8/16/2006 at 3:38:42 PM. Contact: ###-####. called left message 2nd floor anop
|
ELE06-02994
| Electrical Rough-In | 8/17/2006 | 8/17/2006 | 8/17/2006 9:19:05 AM | A | PART |
|
|
ug conduit; all trenches get 8" of gravel and 6" of concrete on top of them; Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack 3 pole lights ok
|
ELE06-03039
| Electrical Rough-In | 8/16/2006 | 8/17/2006 | 8/17/2006 9:15:03 AM | P | CANC |
|
|
underground Internet Inspection Request from: Tyler Bowen Inspection cancelled from web by: Sean DeLacy
|
ELE06-03050
| Final | 8/16/2006 | 8/17/2006 | 8/17/2006 8:37:24 AM | A | PASS |
|
|
Call Jerry @ ###-#### 10 minutes before inspecting. Work performed by Tom Wonacott.; Phone #: ###-#### Internet Inspection Request from: Matt Santacruz
|
ELE06-03059
| Permanent Service | 8/16/2006 | 8/17/2006 | 8/17/2006 8:23:18 AM | A | PASS |
|
|
panel was pulled off in storm. We put a mast head and put panel back on. My cell is ###-####. thanks Randy; Phone #: ###-#### Internet Inspection Request from: Randy Fletcher p/s o/h rec. ok
|
ELE06-03059
| Final | 8/17/2006 | 8/17/2006 | 8/17/2006 8:22:53 AM | A | PASS |
|
|
panel was pulled off in storm. We put a mast head and put panel back on. My cell is ###-####. thanks Randy; Phone #: ###-#### Internet Inspection Request from: Randy Fletcher
|
ELE06-03051
| Electrical Rough-In | 8/16/2006 | 8/17/2006 | 8/17/2006 12:00:00 AM | A | CANC |
|
|
cancel per randy vail//blb DAVE OWEN - PLEASE CALL & HE WILL MEET @ JOBSITE; Phone #: ###-#### Internet Inspection Request from: Randy Vail
|