FIR07-00682
| INSP-Final Inspection | 8/17/2007 | 8/17/2007 | 8/20/2007 4:38:26 PM | P | CANC |
|
|
To be rescheduled
|
BLD07-00948
| FIRE-Final Inspection | 8/17/2007 | 8/17/2007 | 8/17/2007 3:44:57 PM | P | PART |
|
|
This inspection was for the electronics area only. This area is ok to occupy.
|
MIS07-00158
| FIR-Final | 8/17/2007 | 8/17/2007 | 8/17/2007 3:43:27 PM | P | PART |
|
|
A temporary occupancy was given until the fire extinguisher is tagged a sticker is put at the main exit as discussed and lever hardware is installed at the rear exit.
|
BLD07-00376
| FIRE-Final Inspection | 8/17/2007 | 8/17/2007 | 8/17/2007 3:40:22 PM | P | FAIL |
|
|
The wall layout as installed does not match the approved plans. I could not get ahold of Marlene of Jim Storey to see if it was ok to not have resubmittals.
|
BLD07-00377
| FIRE-Final Inspection | 8/17/2007 | 8/17/2007 | 8/17/2007 2:48:00 PM | P | PASS |
|
|
Life safety passed.
|
FIR07-00130
| INSP-Sprinkler Rough-in | 8/16/2007 | 8/17/2007 | 8/17/2007 2:47:29 PM | P | PASS |
|
|
The underspaced heads have been corrected as well as the hangers in the common corridors. The sprinkler piping in the corridors can be covered. The items remaining are the attic system needs to be hydro tested due to the changes and a 24 hour test also the typical final issues such as forward flush, tags, signage.....ect.
|
BLD07-00598
| FIRE-Final Inspection | 8/17/2007 | 8/17/2007 | 8/17/2007 2:23:42 PM | P | PASS |
|
|
Life safety passed
|
BLD07-02047
| FIRE-Final Inspection | 8/16/2007 | 8/17/2007 | 8/17/2007 2:01:00 PM | A | PASS |
|
|
life safety passed
|
BLD07-00491
| FIRE-Final Inspection | 8/17/2007 | 8/17/2007 | 8/17/2007 1:41:30 PM | P | PART |
|
|
A temporary occupancy was given with dave hannimans permission until the hvac unit is installed and a fire alarm permit is issued
|
FIR07-00459
| INSP-Supply line flush | 8/16/2007 | 8/17/2007 | 8/17/2007 1:32:23 PM | A | PASS |
|
|
The underground flush and hydro test passed.
|
FIR07-00163
| INSP-Sprinkler Rough-in | 8/15/2007 | 8/17/2007 | 8/17/2007 1:22:01 PM | A | PASS |
|
|
See the city approved plans for locations where the spirnkler piping is ok to cover. Ceilings will need to be added in the mechanical closets or the walls will need to extend to the deck. The upright will not suffice. A separation is needed between the sprinklered area and the non-sprinklered area
|
FIR05-00536
| INSP-Sprinkler Rough-in/Hydro | 8/16/2007 | 8/17/2007 | 8/17/2007 12:24:47 PM | A | PASS |
|
|
6th and 7th floor hydro tests passed
|
FIR07-00381
| INSP-Final Inspection | 8/16/2007 | 8/17/2007 | 8/17/2007 8:49:32 AM | A | PASS |
|
|
Permit finaled
|
FIR07-00545
| INSP-Final Inspection | 8/16/2007 | 8/17/2007 | 8/17/2007 7:44:09 AM | A | PASS |
|
|
permit finaled
|