FIR07-00315
| FIR-Aging Inspection | 8/17/2010 | 8/17/2010 | 8/19/2010 1:10:12 PM | | DONE |
|
|
Site work in progress.
|
FIR07-00371
| FIR-Aging Inspection | 8/17/2010 | 8/17/2010 | 8/19/2010 1:03:17 PM | | DONE |
|
|
Construction suspended.
|
BLD10-01112
| FIRE-Final Inspection | 8/17/2010 | 8/17/2010 | 8/17/2010 4:55:02 PM | P | PART |
|
|
Temporary occupancy approved for a term of 30 days per M. Senteno. Note: System impairments beyond eight hours will require a fire watch.
|
FIR10-00319
| INSP-Final Inspection | 8/17/2010 | 8/17/2010 | 8/17/2010 4:52:18 PM | P | PART |
|
|
Temporary occupancy approval okayed per M. Senteno.
|
FIR10-00358
| INSP-Conference | 8/17/2010 | 8/17/2010 | 8/17/2010 4:51:58 PM | P | PART |
|
|
Temporary occupancy approval okayed per M. Senteno.
|
FIR10-00341
| INSP-Sprinkler Rough-in | 8/17/2010 | 8/17/2010 | 8/17/2010 3:47:34 PM | P | PART |
|
|
Overhead fire sprinkler work per the scope of remodel is approved for cover at the drop ceilings.
|
FIR10-00342
| INSP-Sprinkler Rough-in/Hydro | 8/13/2010 | 8/17/2010 | 8/17/2010 3:46:24 PM | P | PART |
|
|
Overhead hydrostatic test of the new antifreeze system passed.
|
FIR10-00372
| INSP-Final Inspection | 8/13/2010 | 8/17/2010 | 8/17/2010 1:06:10 PM | A | PART |
|
|
Overhead sprinkler system modifications okayed with the exception of three missing retainer straps at new top beam clamps for armover hangers and one overspaced pendent head to an adjacent wall. See stamped plan set for locations. Remainder of work approved for cover. Need to verify existing system is current with an annual inspection.
|
FIR10-00322
| INSP-Sprinkler Rough-in | 8/16/2010 | 8/17/2010 | 8/17/2010 1:01:35 PM | A | PART |
|
|
Seismic bracing inspection passed- okay to replace insulation at the truss members.
|
BLD09-01722
| FIRE-Final Inspection | 8/16/2010 | 8/17/2010 | 8/17/2010 12:59:46 PM | A | PASS |
|
|
Fire life safety inspection passed.
|
BLD09-01723
| FIRE-Final Inspection | 8/16/2010 | 8/17/2010 | 8/17/2010 12:59:07 PM | A | PASS |
|
|
Fire life safety inspection passed.
|
BLD10-01453
| FIRE-Final Inspection | 8/16/2010 | 8/17/2010 | 8/17/2010 12:58:06 PM | A | PASS |
|
|
Life safety inspection completed acceptable.
|