Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00315 FIR-Aging Inspection8/17/20108/17/20108/19/2010 1:10:12 PM DONE
Site work in progress.
FIR07-00371 FIR-Aging Inspection8/17/20108/17/20108/19/2010 1:03:17 PM DONE
Construction suspended.
BLD10-01112 FIRE-Final Inspection8/17/20108/17/20108/17/2010 4:55:02 PMPPART
Temporary occupancy approved for a term of 30 days per M. Senteno. Note: System impairments beyond eight hours will require a fire watch.
FIR10-00319 INSP-Final Inspection8/17/20108/17/20108/17/2010 4:52:18 PMPPART
Temporary occupancy approval okayed per M. Senteno.
FIR10-00358 INSP-Conference8/17/20108/17/20108/17/2010 4:51:58 PMPPART
Temporary occupancy approval okayed per M. Senteno.
FIR10-00341 INSP-Sprinkler Rough-in8/17/20108/17/20108/17/2010 3:47:34 PMPPART
Overhead fire sprinkler work per the scope of remodel is approved for cover at the drop ceilings.
FIR10-00342 INSP-Sprinkler Rough-in/Hydro8/13/20108/17/20108/17/2010 3:46:24 PMPPART
Overhead hydrostatic test of the new antifreeze system passed.
FIR10-00372 INSP-Final Inspection8/13/20108/17/20108/17/2010 1:06:10 PMAPART
Overhead sprinkler system modifications okayed with the exception of three missing retainer straps at new top beam clamps for armover hangers and one overspaced pendent head to an adjacent wall. See stamped plan set for locations. Remainder of work approved for cover. Need to verify existing system is current with an annual inspection.
FIR10-00322 INSP-Sprinkler Rough-in8/16/20108/17/20108/17/2010 1:01:35 PMAPART
Seismic bracing inspection passed- okay to replace insulation at the truss members.
BLD09-01722 FIRE-Final Inspection8/16/20108/17/20108/17/2010 12:59:46 PMAPASS
Fire life safety inspection passed.
BLD09-01723 FIRE-Final Inspection8/16/20108/17/20108/17/2010 12:59:07 PMAPASS
Fire life safety inspection passed.
BLD10-01453 FIRE-Final Inspection8/16/20108/17/20108/17/2010 12:58:06 PMAPASS
Life safety inspection completed acceptable.