Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR12-00237 INSP-Alarm Testing8/15/20128/15/2012 P 
Please call 30 min prior to arrival Phone #: ###-#### >> Inspection requested via web by Jeff Walton
FIR12-00330 INSP-Sprinkler Rough-in8/17/20128/17/20128/17/2012 5:00:09 PMPPART
Verified thrust blocking for the relocated 90 and 45 ells at the property line. UG okayed for cover.
BLD12-01297 FIRE-Final Inspection8/17/20128/17/20128/17/2012 4:56:46 PMPFAIL
Missing exit signs and EM lighting per plan, need to post fire extinguishers, provide approved door hardware at locations shown per plan, provide knox box per fire code review comments.
BLD12-01302 FIRE-Final Inspection8/16/20128/17/20128/17/2012 3:13:18 PMPNR
Project related fire alarm permit is in review status, also need fire sprinkler permit final.
BLD12-01832 FIRE-Final Inspection8/17/20128/17/20128/17/2012 2:48:23 PMPPASS
Fire life safety passed. Project related fire alarm work also passed re-inspection.
FIR12-00376 INSP-Final Inspection8/16/20128/17/20128/17/2012 2:47:00 PMAPASS
Remainder of fire alarm work passed functional testing. Permit finaled.
FIR12-00347 INSP-Final Inspection8/16/20128/17/20128/17/2012 2:45:39 PMAPASS
Correction items verified for completion. Fire sprinkler permit finaled.
FIR12-00247 INSP-Sprinkler Rough-in/Hydro8/16/20128/17/20128/17/2012 2:44:38 PMAPART
UG fire supply line hydrostatic test for building 10 passed.
BLD12-02001 FIRE-Final Inspection8/16/20128/17/20128/17/2012 2:43:25 PMAFAIL
Missing fire sprinkler coverage at one storage closet, overspaced sprinkler coverage at the lobby, need to verify current annual certification of the existing system, also need hardware revisions at the warehouse exit door south side.
BLD12-02018 FIRE-Final Inspection8/16/20128/17/20128/17/2012 2:39:14 PMPPASS
Fire life safety inspection passed. Noted correction items are complete.