FIR12-00237
| INSP-Alarm Testing | 8/15/2012 | 8/15/2012 | | P | |
|
|
Please call 30 min prior to arrival Phone #: ###-#### >> Inspection requested via web by Jeff Walton
|
FIR12-00330
| INSP-Sprinkler Rough-in | 8/17/2012 | 8/17/2012 | 8/17/2012 5:00:09 PM | P | PART |
|
|
Verified thrust blocking for the relocated 90 and 45 ells at the property line. UG okayed for cover.
|
BLD12-01297
| FIRE-Final Inspection | 8/17/2012 | 8/17/2012 | 8/17/2012 4:56:46 PM | P | FAIL |
|
|
Missing exit signs and EM lighting per plan, need to post fire extinguishers, provide approved door hardware at locations shown per plan, provide knox box per fire code review comments.
|
BLD12-01302
| FIRE-Final Inspection | 8/16/2012 | 8/17/2012 | 8/17/2012 3:13:18 PM | P | NR |
|
|
Project related fire alarm permit is in review status, also need fire sprinkler permit final.
|
BLD12-01832
| FIRE-Final Inspection | 8/17/2012 | 8/17/2012 | 8/17/2012 2:48:23 PM | P | PASS |
|
|
Fire life safety passed. Project related fire alarm work also passed re-inspection.
|
FIR12-00376
| INSP-Final Inspection | 8/16/2012 | 8/17/2012 | 8/17/2012 2:47:00 PM | A | PASS |
|
|
Remainder of fire alarm work passed functional testing. Permit finaled.
|
FIR12-00347
| INSP-Final Inspection | 8/16/2012 | 8/17/2012 | 8/17/2012 2:45:39 PM | A | PASS |
|
|
Correction items verified for completion. Fire sprinkler permit finaled.
|
FIR12-00247
| INSP-Sprinkler Rough-in/Hydro | 8/16/2012 | 8/17/2012 | 8/17/2012 2:44:38 PM | A | PART |
|
|
UG fire supply line hydrostatic test for building 10 passed.
|
BLD12-02001
| FIRE-Final Inspection | 8/16/2012 | 8/17/2012 | 8/17/2012 2:43:25 PM | A | FAIL |
|
|
Missing fire sprinkler coverage at one storage closet, overspaced sprinkler coverage at the lobby, need to verify current annual certification of the existing system, also need hardware revisions at the warehouse exit door south side.
|
BLD12-02018
| FIRE-Final Inspection | 8/16/2012 | 8/17/2012 | 8/17/2012 2:39:14 PM | P | PASS |
|
|
Fire life safety inspection passed. Noted correction items are complete.
|