Inspections for the day of: Wednesday, August 17, 2016.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-00936 ELE-Aging Inspection8/17/20168/17/20168/25/2016 2:49:24 PM PASS
Waiting on contractor
ELE16-02600 Electrical Rough-In8/17/20168/17/20168/18/2016 8:19:28 AMPDONE
2nd Floor Rough Phone #: ###-#### Inspection requested via web by Buster Bowen discussed 210.60 clarification on code reference. Conference only As per Daryl Degrange the required outlets shall follow 210.52 and the minimum number of receptacles is not permitted to be reduced and should be determined by assuming the furniture is not in place.
MIS16-00257 ELE-Conference8/17/20168/17/20168/17/2016 4:27:59 PMPCANC
Kevin-- Please call before** Kevin knows that Eric created MIS***Per Eric Strole- extra plumbing, mechanical and electrical work being done without a permit Phone #: ###-#### reschedule for next day
ELE16-02654 Electrical Rough-In8/16/20168/17/20168/17/2016 4:27:58 PMPPASS
Phone #: ###-#### Inspection requested via web by kendall bender level 2 prep room and serving room Walls only. Panel and lighting by others.
ELE16-01838 Electrical Rough-In8/16/20168/17/20168/17/2016 3:28:44 PMPPASS
Level 5 stack 1 headquarters , Lab walls. Call John Phone #: ###-#### Inspection requested via web by Brandon Robinson area as noted wall roughin ok
ELE15-03901 Electrical Rough-In8/17/20168/17/20168/17/2016 2:58:28 PMPPASS
Call Rafael for inspection of office furniture on 8th floor. Phone #: ###-#### Inspection requested via web by Rafael Castillo furniture ok as noted on contractor prints.
ELE15-00495 Electrical Rough-In8/17/20168/17/20168/17/2016 2:57:45 PMPPASS
Wall rough in Stair 5 Floors 5,4,3 possibly 2.
Contact is Eric Gibson ###-####. Phone #: ###-#### Inspection requested via web by Toby Groves core and shell stairwell number 5 floors 2-5 roughin ok to cover
ELE16-00089 Electrical Rough-In8/17/20168/17/20168/17/2016 2:56:32 PMAPASS
Rough-in inspection of walls on 4th and 5th floor around stairwell 5. Call Bob for inspection. Phone #: ###-#### Inspection requested via web by Rafael Castillo areas as noted plus elevator walls. Fixture on drop cloud ceiling shall have access to splice points and shall provide proof ceiling system is rated for weight.
ELE16-01946 Electrical Rough-In8/16/20168/17/20168/17/2016 10:46:58 AMAPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton West offices and a few SW offices ok for cover as noted on contractor print.
ELE16-00983 Final8/16/20168/17/20168/17/2016 10:08:39 AMANR
Michael (Betty''s son) Phone #: ###-#### Main service ok, garage wiring yet to be done. Owner to add garage to existing permit. Notified homeowner about this process.
ELE16-00983 ELE-Request for Extension8/17/20168/17/20168/17/2016 10:06:50 AMPPASS
Michael (Betty''s son) Phone #: ###-#### Existing garage burned. New panel in garage to be wired in the future. Underground ok
ELE16-02626 Electrical Rough-In8/16/20168/17/20168/17/2016 9:43:47 AMAFAIL
key in lock box by front entrance. code is 2173 Phone #: ###-#### Inspection requested via web by Paula Gratiot Failed for the following-
210.52 dining outlet needs added in open wall.
314.23(B)(1) replace boxes in multiple locations that have screws driven through the box for support.
210.11(C)(3) Walls are open in up bath, need to update 20a GFI circuit supplying vanity. 4. 210.52 outlet needs added to left of sliding door upstairs, over 6'.
ELE16-01107 Final8/16/20168/17/20168/17/2016 9:01:36 AMAPASS
This is a final inspection on a pool. The owner is Joe Illingworth and his number is ###-####. Phone #: ###-#### Inspection requested via web by Warren Fry Final ok