Inspections for the day of: Wednesday, August 17, 2016.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00107 INSP-Sprinkler Rough-in/Hydro8/17/20168/17/20168/17/2016 1:56:16 PMPPASS
Overhead hydro passed
FIR16-00500 INSP-Final Inspection8/17/20168/17/20168/17/2016 10:32:03 AMPPASS
Permit finaled
BLD16-02315 FIRE-Final Inspection8/17/20168/17/20168/17/2016 10:30:57 AMPPASS
life safety passed
BLD16-02377 FIRE-Final Inspection8/17/20168/17/20168/17/2016 10:30:12 AMPPASS
life safety passed
FIR16-00152 INSP-Final Inspection8/15/20168/17/20168/17/2016 10:28:12 AMAFAIL
Not ready for a final yet. Need hydro test, need siesmic bracing at the top of riser, need coverage in the combustible concealed space, need upright uncovered in the server room, possibly need additional head in the Server room
FIR16-00211 INSP-Final Inspection8/17/20168/17/20168/17/2016 9:00:26 AMPPASS
permit finaled
FIR16-00211 INSP-Sprinkler Rough-in/Hydro8/17/20168/17/20168/17/2016 9:00:03 AMPCANC
Wrong inspection type scheduled
FIR16-00211 INSP-Sprinkler Rough-in/Hydro8/16/20168/17/20168/17/2016 8:59:17 AMPCANC
Wrong inspection type scheduled
FIR16-00045 INSP-Final Inspection8/16/20168/17/20168/17/2016 8:50:26 AMPPASS
Permit finaled
FIR16-00045 INSP-Final Inspection8/16/20168/17/20168/17/2016 8:49:48 AMAPASS
Permit finaled.