FIR16-00322 INSP-Sprinkler Rough-in/Hydro8/17/20168/17/20168/17/2016 12:53:41 PMPPASS
200 psi hydrostatic test for standpipe complete
FIR15-00808 INSP-Sprinkler Rough-in8/16/20168/17/20168/17/2016 11:40:26 AMPPASS
Tenting inspection for overhead fire sprinkler piping located in attic spaces complete, overhead fire sprinkler piping located in attic area's approved for cover.
FIR16-00496 INSP-Sprinkler Rough-in/Hydro8/16/20168/17/20168/17/2016 11:27:48 AMAPASS
200 psi hydrostatic test complete for dry system. Rough to cover inspection for dry system protecting the east side canopy complete, Overhead fire sprinkler piping located above hardlid in east side canopy approved for cover.
BLD16-00476 FIRE-Final Inspection8/16/20168/17/20168/17/2016 9:01:24 AMAPASS
Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguishers are in common area's with current inspection tags. Final life fire safety inspection passed/complete.
FIR16-00256 INSP-Final Inspection8/17/20168/17/20168/17/2016 9:00:30 AMPPASS
Final fire sprinkler inspection passed/complete
FIR16-00516 INSP-Final Inspection8/16/20168/17/20168/16/2016 6:10:02 PMACANC
Inspecting Technician: Ray McQueen
Building Access: open & available Phone #: ###-#### >> Inspection requested via web by Rose Peterson Inspection cancelled from web by: Rose Peterson
BLD16-02487 FIRE-Final Inspection8/16/20168/17/20168/16/2016 2:29:39 PMACANC
Call Jason to walk thru. Phone #: ###-#### >> Inspection requested via web by Ami Tracy Inspection cancelled from web by: Ami Tracy