BLD17-00577
| FIRE-Final Inspection | 8/17/2017 | 8/17/2017 | 8/17/2017 1:18:03 PM | P | CANC |
|
|
Duplicate inspection request, this request is cancelled.
|
BLD17-00577
| FIRE-Final Inspection | 8/16/2017 | 8/17/2017 | 8/17/2017 1:17:33 PM | A | FAIL |
|
|
Exit signs/emergency lighting need to be installed per city approved plans in area of work. Exit discharge egress lighting needs to be installed on south exterior exit in area of work.
|
BLD17-01901
| FIRE-Final Inspection | 8/17/2017 | 8/17/2017 | 8/17/2017 12:51:45 PM | P | PASS |
|
|
No fire sprinkler modifications, fire alarm work completed under FIR16-00222 and will be included in the as-builts, fire extinguisher is in common area with a current inspection tag. Final life fire safety inspection for area of work passed/complete.
|
FIR17-00427
| INSP-Sprinkler Rough-in | 8/16/2017 | 8/17/2017 | 8/17/2017 12:45:50 PM | A | PASS |
|
|
Rough to cover inspection for underground supply complete, approved for cover.
|
BLD16-04266
| FIRE-Final Inspection | 8/17/2017 | 8/17/2017 | 8/17/2017 11:51:25 AM | A | FAIL |
|
|
Fire extinguisher needs to be added in area of work per note number 5 of the builing permit fire code review. Nearest fire extinguisher is located in elevator lobby area.
|
FIR16-00222
| INSP-Sprinkler Rough-in/Hydro | 8/16/2017 | 8/17/2017 | 8/17/2017 10:43:31 AM | A | PASS |
|
|
Final fire alarm inspection for phase 1 passed/complete. Modifications to room 106 for ADA compliance and the addition of smoke detector in room 301 will be included on the as-builts for fire alarms.
|
BLD17-00639
| FIRE-Final Inspection | 8/16/2017 | 8/17/2017 | 8/17/2017 9:02:25 AM | A | PASS |
|
|
Fire sprinkler inspection complete, fire alarm inspection complete (see notes for fire alarm explanation under FIR17-00350), fire extinguishers are in place with current inspection tags. Final life fire safety inspection for area of work passed/complete.
|
FIR17-00350
| INSP-Final Inspection | 8/17/2017 | 8/17/2017 | 8/17/2017 9:01:28 AM | A | PASS |
|
|
Area of work does have active fire alarms throughout tenant space, audio alarms do not have 3 temporal throughout space. Contractor is working with building manager/property owners to upgrade fire alarm system upgrade to address notification issues. Final fire alarm inspection for this area of work complete, any other future work throughout building that occurs and fire alarm issues are not resloved will result in an inspection failure.
|
FIR17-00282
| INSP-Final Inspection | 8/17/2017 | 8/17/2017 | 8/17/2017 8:52:58 AM | A | PASS |
|
|
Final fire sprinkler inspection for area of work passed/complete
|
BLD17-00665
| FIRE-Conference | 8/16/2017 | 8/17/2017 | 8/17/2017 8:51:22 AM | A | DONE |
|
|
Fire conference complete
|
FIR16-00586
| INSP-Sprinkler Rough-in | 8/16/2017 | 8/17/2017 | 8/17/2017 8:22:13 AM | A | PART |
|
|
Rough to cover inspection for overhead fire sprinkler piping/tenting on level 5 south of the elevator shate complete, level 5 south of elevator shaft approved for cover.
|
FIR17-00003
| INSP-Final Inspection | 8/17/2017 | 8/17/2017 | 8/17/2017 7:40:42 AM | A | PASS |
|
|
Final fire alarm inspection passed/complete for area's of work. Mag-locks on doors released under general fire alarm.
|