Inspections for the day of: Thursday, August 17, 2017.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD17-00577 FIRE-Final Inspection8/17/20178/17/20178/17/2017 1:18:03 PMPCANC
Duplicate inspection request, this request is cancelled.
BLD17-00577 FIRE-Final Inspection8/16/20178/17/20178/17/2017 1:17:33 PMAFAIL
Exit signs/emergency lighting need to be installed per city approved plans in area of work. Exit discharge egress lighting needs to be installed on south exterior exit in area of work.
BLD17-01901 FIRE-Final Inspection8/17/20178/17/20178/17/2017 12:51:45 PMPPASS
No fire sprinkler modifications, fire alarm work completed under FIR16-00222 and will be included in the as-builts, fire extinguisher is in common area with a current inspection tag. Final life fire safety inspection for area of work passed/complete.
FIR17-00427 INSP-Sprinkler Rough-in8/16/20178/17/20178/17/2017 12:45:50 PMAPASS
Rough to cover inspection for underground supply complete, approved for cover.
BLD16-04266 FIRE-Final Inspection8/17/20178/17/20178/17/2017 11:51:25 AMAFAIL
Fire extinguisher needs to be added in area of work per note number 5 of the builing permit fire code review. Nearest fire extinguisher is located in elevator lobby area.
FIR16-00222 INSP-Sprinkler Rough-in/Hydro8/16/20178/17/20178/17/2017 10:43:31 AMAPASS
Final fire alarm inspection for phase 1 passed/complete. Modifications to room 106 for ADA compliance and the addition of smoke detector in room 301 will be included on the as-builts for fire alarms.
BLD17-00639 FIRE-Final Inspection8/16/20178/17/20178/17/2017 9:02:25 AMAPASS
Fire sprinkler inspection complete, fire alarm inspection complete (see notes for fire alarm explanation under FIR17-00350), fire extinguishers are in place with current inspection tags. Final life fire safety inspection for area of work passed/complete.
FIR17-00350 INSP-Final Inspection8/17/20178/17/20178/17/2017 9:01:28 AMAPASS
Area of work does have active fire alarms throughout tenant space, audio alarms do not have 3 temporal throughout space. Contractor is working with building manager/property owners to upgrade fire alarm system upgrade to address notification issues. Final fire alarm inspection for this area of work complete, any other future work throughout building that occurs and fire alarm issues are not resloved will result in an inspection failure.
FIR17-00282 INSP-Final Inspection8/17/20178/17/20178/17/2017 8:52:58 AMAPASS
Final fire sprinkler inspection for area of work passed/complete
BLD17-00665 FIRE-Conference8/16/20178/17/20178/17/2017 8:51:22 AMADONE
Fire conference complete
FIR16-00586 INSP-Sprinkler Rough-in8/16/20178/17/20178/17/2017 8:22:13 AMAPART
Rough to cover inspection for overhead fire sprinkler piping/tenting on level 5 south of the elevator shate complete, level 5 south of elevator shaft approved for cover.
FIR17-00003 INSP-Final Inspection8/17/20178/17/20178/17/2017 7:40:42 AMAPASS
Final fire alarm inspection passed/complete for area's of work. Mag-locks on doors released under general fire alarm.