Inspections for the day of: Friday, August 17, 2018.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-01283 Final8/16/20188/17/20188/17/2018 1:57:45 PMPFAIL
Phone #: ###-#### Inspection requested via web by Troy Cobb
BCC 04-05-32- No code violation shall be retained. Hot tub TA, Bonding rain gutter, Missing covers and outdoor covers.
110.3- Reverse polarity washer receptacle.
110.27- All NM located below 8' shall be protected from damage. Master bath, above panel.
210.8- Washer receptacle located with in 6' of a sink shall have GFCI protection.
210.52- Receptacles shall serve wall space 24" and wider and no point measured along floor line shall be more than 6' from a receptacle outlet. Down stairs bed each side of door, master bed each side of fireplace 6' of wall space each side. Room straight back from entry over 12' between receptacle and 1 recept. not workng.
314.20- Spark rings needed for receptacles located in stone where boxes 1/4" or more in non combustible materials.
406.6- All receptacles shall have covers, outdoor back of house and master bed.
410.16- Recessed cons located in master closet area shall have totally enclosed lamps.
680.26(B)(7)- Fixed metal located with in 5" horizontal and 12" vertical of hot tub water edge shall be bonded to hot tub equipment.
ELE18-03060 Rough-In Permanent Service8/16/20188/17/20188/17/2018 12:02:27 PMAFAIL
Phone #: ###-#### Inspection requested via web by Bob Glenn
300.4- Where NM cable is run thru bored holes that do not maintain 1 1/4" from framing surface they shall be protected form physical damage. Understairand nook.
314.25- Recessed junction box cover shall be installed as per instructions. Out master entrance.
334.12-NM cable shall not be installed where subject to physical damage. Above drywall stop on stairs and in front of stud in laundry rm. Fan S/L and travellers.
350.30- LFMC shall be secured in place with in 12" of termination of a box and fireplace.
ELE17-02862 Electrical Rough-In8/17/20188/17/20188/17/2018 10:35:06 AMAPASS
Lobby,storage , bike room , trash room . etc rest of 1st floor
Phone #: ###-#### Inspection requested via web by Tom Betty
Areas noted plus mail rm, and move in room, vanilla TI space rough in ok cover
ELE18-02777 Electrical Rough-In8/16/20188/17/20188/17/2018 10:33:28 AMAPASS
Rough in front entry Phone #: ###-#### Inspection requested via web by Ryan Wake Entrance walls and hardlid and cloud rough in ok cover
ELE18-02423 Electrical Rough-In8/16/20188/17/20188/17/2018 9:36:57 AMAPART
Above ceiling grid inspection. Dustin is the contact at ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Kerri Hamilton
South cloud only rough in ok cover
ELE18-03133 Electrical Rough-In8/16/20188/17/20188/17/2018 9:09:43 AMAPASS
Need underground inspection on Trench gate code is 5472# be careful of the overly friendly dogs they may lick you to death and then beg food from you. can see shop slab on left as you enter driveway Trench is at back corner Phone #: ###-#### Inspection requested via web by TRENT Swaim
Underground from back shed to shop rough in ok cover
ELE18-03058 Electrical Rough-In8/16/20188/17/20188/17/2018 8:44:30 AMAPASS
I could not see a selection for underground inspection however I do need Underground conduit inspected from the house to the garage Inspection requested via web by TRENT Swaim Underground to shop rough in ok cover