Inspections for the day of: Monday, August 18, 2003.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD03-01459 FIRE-Final Inspection8/15/20038/18/20038/18/2003 12:00:00 AMAFAIL
TAMMY; Phone #: ###-#### Provide approved door hardware all doors.
Move fire extinguisher to 48". 8/18/2003 10:35:17 AM 8/18/2003 10:35:39 AM
MIS03-00155 FIR-Final8/15/20038/18/20038/18/2003 12:00:00 AMAFAIL
###-#### KELLY Sprinkler pendants are overspaced in areas marked on plans, missing canopies on sprinkler head, repiar exit sign, provide verification of annual sprinkler inspection 8/18/2003 11:45:31 AM
FIR03-00429 INSP-Final Inspection8/15/20038/18/20038/18/2003 12:00:00 AMAPASS
MARK; Phone #: ###-#### Internet Inspection Request from: Darla Downs
BLD03-01176 FIRE-Final Inspection8/18/20038/18/20038/18/2003 12:00:00 AMAPASS
fire life safety finaled 8/18/2003 10:51:03 AM
BLD02-01077 BLD-Conference8/18/20038/18/20038/18/2003 12:00:00 AMADONE
I spoke to John with Treasure Valley Fire and he said he would follow up on work being completed 8/18/2003 10:43:42 AM
BLD03-01351 FIRE-Final Inspection8/18/20038/18/20038/18/2003 12:00:00 AMAPASS
Fire life safety finaled
BLD03-01000 FIRE-Final Inspection8/18/20038/18/20038/18/2003 12:00:00 AMAPASS
Fire life safety finaled
FIR03-00389 INSP-Final Inspection8/18/20038/18/20038/18/2003 12:00:00 AMAPASS
FIR02-00360 INSP-Conference8/18/20038/18/20038/18/2003 12:00:00 AMADONE
I spoke to John with Treasure Valley Fire and he said he would follow up on work being completed
MIS03-00155 FIR-Final8/18/20038/18/20038/18/2003 12:00:00 AMPCANC
duplicate inspection 8/18/2003 11:53:49 AM
FIR02-00478 INSP-Final Inspection8/18/20038/18/20038/18/2003 12:00:00 AMPPASS
FIR02-00405 INSP-Final Inspection8/18/20038/18/20038/18/2003 12:00:00 AMPPASS
BLD01-02706 FIRE-Final Inspection8/18/20038/18/20038/18/2003 12:00:00 AMPPASS
Fire life safety, fire alarm and fire sprinkler finaled 8/18/2003 1:27:58 PM
FIR03-00206 INSP-Sprinkler Rough-in8/18/20038/18/20038/18/2003 12:00:00 AMPPART
MIKE ###-#### I looked at the piping in the high ceiling area that runs east/west and it is ok to cover. The piping as installed in the high ceiling areas that run north/south do not match plans and need to be resubmitted 8/18/2003 4:20:18 PM
BLD03-00722 FIRE-Final Inspection8/14/20038/18/20038/18/2003 12:00:00 AMPFAIL
Provide verification of IFC sections 3203.2.6, 3203.4.4, 3203.4.6. Provide NFPA 704 markings for the tank. Provide verification of fail safe controls per review note 4, IFC 3005.2 8/18/2003 3:05:13 PM