Inspections for the day of: Wednesday, August 18, 2004.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00738 FIR-Aging Inspection8/18/20048/18/20048/18/2004 12:00:00 AM NR
per fire alarm contractor the fire alarm system is not installed yet 8/18/2004 8:43:38 AM
BLD04-01601 FIRE-Final Inspection8/17/20048/18/20048/18/2004 12:00:00 AMAFAIL
Get fire extinguisher inspected. Provide approved door hardware on restroom and office doors. Provide sticker at the main exit. 8/18/2004 11:51:34 AM
BLD04-01049 FIRE-Alarm Testing8/17/20048/18/20048/18/2004 12:00:00 AMAFAIL
Test hood system. Repair of remove the emergency light. Provide canopies for sprinkler pendants. Provide ceiling tile for sprinkler pendants. Repair the smoke evacuation louver. 8/18/2004 8:55:19 AM
FIR04-00411 INSP-Sprinkler Rough-in8/17/20048/18/20048/18/2004 12:00:00 AMAFAIL
Resubmit plans showing wall changes. Can't use small room rule in will call/ shipping area. See plans for location. More than one pendant off of 1" outlet over restroom 8/18/2004 3:25:04 PM
FIR03-00468 INSP-Sprinkler Rough-in/Hydro8/17/20048/18/20048/18/2004 12:00:00 AMACANC
Scheduled by a contractor via Hello! on 8/17/2004 at 11:42:05 AM. Contact: ###-####.
FIR04-00291 INSP-Final Inspection8/17/20048/18/20048/18/2004 12:00:00 AMAPASS
permit finaled 8/18/2004 9:50:41 AM
BLD04-01559 FIRE-Final Inspection8/17/20048/18/20048/18/2004 12:00:00 AMAFAIL
Remove thumbturn on the main entry/exit. Keyed hardware (lock) on both sides is OK. Provide sticker at main exit. Remove thumbturn from rear exit. Repair or replace inoperative exit sign and emergency lights. Mount and tag fire extinguisher. Provide approved door hardware for all doors. Lever type is ok. Lift sagging insulation at sprinkler uprights and remove or relocate the extra sprinkler pendant that is spaced less than 6' from another pendant.. Work will require permits. It does not appear any review notes have been read. 8/18/2004 11:54:40 AM
BLD04-00086 FIRE-Final Inspection8/17/20048/18/20048/18/2004 12:00:00 AMPFAIL
Provide permanant suite number. Provide fire extinguisher per review note #2. Provide occupant load sign per review note #8. Provide verification of note #25 8/18/2004 3:27:05 PM
BLD04-01020 FIRE-Final Inspection8/17/20048/18/20048/17/2004 12:00:00 AMPCANC
Scheduled by a contractor via Hello! on 8/17/2004 at 2:38:38 PM. Contact: ###-####. Ivan called canc inspection 4:20