FIR03-00738
| FIR-Aging Inspection | 8/18/2004 | 8/18/2004 | 8/18/2004 12:00:00 AM | | NR |
|
|
per fire alarm contractor the fire alarm system is not installed yet 8/18/2004 8:43:38 AM
|
BLD04-01601
| FIRE-Final Inspection | 8/17/2004 | 8/18/2004 | 8/18/2004 12:00:00 AM | A | FAIL |
|
|
Get fire extinguisher inspected. Provide approved door hardware on restroom and office doors. Provide sticker at the main exit. 8/18/2004 11:51:34 AM
|
BLD04-01049
| FIRE-Alarm Testing | 8/17/2004 | 8/18/2004 | 8/18/2004 12:00:00 AM | A | FAIL |
|
|
Test hood system. Repair of remove the emergency light. Provide canopies for sprinkler pendants. Provide ceiling tile for sprinkler pendants. Repair the smoke evacuation louver. 8/18/2004 8:55:19 AM
|
FIR04-00411
| INSP-Sprinkler Rough-in | 8/17/2004 | 8/18/2004 | 8/18/2004 12:00:00 AM | A | FAIL |
|
|
Resubmit plans showing wall changes. Can't use small room rule in will call/ shipping area. See plans for location. More than one pendant off of 1" outlet over restroom 8/18/2004 3:25:04 PM
|
FIR03-00468
| INSP-Sprinkler Rough-in/Hydro | 8/17/2004 | 8/18/2004 | 8/18/2004 12:00:00 AM | A | CANC |
|
|
Scheduled by a contractor via Hello! on 8/17/2004 at 11:42:05 AM. Contact: ###-####.
|
FIR04-00291
| INSP-Final Inspection | 8/17/2004 | 8/18/2004 | 8/18/2004 12:00:00 AM | A | PASS |
|
|
permit finaled 8/18/2004 9:50:41 AM
|
BLD04-01559
| FIRE-Final Inspection | 8/17/2004 | 8/18/2004 | 8/18/2004 12:00:00 AM | A | FAIL |
|
|
Remove thumbturn on the main entry/exit. Keyed hardware (lock) on both sides is OK. Provide sticker at main exit. Remove thumbturn from rear exit. Repair or replace inoperative exit sign and emergency lights. Mount and tag fire extinguisher. Provide approved door hardware for all doors. Lever type is ok. Lift sagging insulation at sprinkler uprights and remove or relocate the extra sprinkler pendant that is spaced less than 6' from another pendant.. Work will require permits. It does not appear any review notes have been read. 8/18/2004 11:54:40 AM
|
BLD04-00086
| FIRE-Final Inspection | 8/17/2004 | 8/18/2004 | 8/18/2004 12:00:00 AM | P | FAIL |
|
|
Provide permanant suite number. Provide fire extinguisher per review note #2. Provide occupant load sign per review note #8. Provide verification of note #25 8/18/2004 3:27:05 PM
|
BLD04-01020
| FIRE-Final Inspection | 8/17/2004 | 8/18/2004 | 8/17/2004 12:00:00 AM | P | CANC |
|
|
Scheduled by a contractor via Hello! on 8/17/2004 at 2:38:38 PM. Contact: ###-####. Ivan called canc inspection 4:20
|