Inspections for the day of: Thursday, August 18, 2005.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR02-00388 FIR-Aging Inspection8/18/20058/18/20058/19/2005 10:52:49 AM NR
I spoke to brad at treasure valley he will follow up.
BLD04-00709 FIRE-Final Inspection8/18/20058/18/20058/18/2005 4:40:05 PMPFAIL
Final the fire sprinkler permit. Provide occupant load signs per review note #27. Provide one additional extinguisher in the northwest corner of the gym. Provide exit discharge lighting as discussed at each exit from the new building per building review comments note #46. Provide signage for fire access as shown on sheet A1.0
BLD05-00347 FIRE-Final Inspection8/17/20058/18/20058/18/2005 4:37:27 PMAFAIL
I went over life safety items with the contractor. No inspection.
BLD05-00236 FIRE-Final Inspection8/17/20058/18/20058/18/2005 3:56:06 PMPFAIL
Provide the correct remote annunciators for the duct smoke detectors and turn the sample tubes per the manufacturers recommendations into the airstream for proper sampling.
FIR04-00737 INSP-Sprinkler Rough-in/Hydro8/18/20058/18/20058/18/2005 3:11:31 PMPCANC
Wrong permit called in. See FIR 05-00124
FIR05-00427 INSP-Final Inspection8/18/20058/18/20058/18/2005 2:54:59 PMPPASS
Hood suppression systems operated correctly
FIR04-00718 INSP-Final Inspection8/18/20058/18/20058/18/2005 2:24:14 PMPPASS
Fire alarm permit finaled
FIR05-00415 INSP-Sprinkler Rough-in8/18/20058/18/20058/18/2005 12:12:51 PMPPASS
Overhead piping inspected only. Tenting passed. Dave was to tent the riser piping that penatrates the garage ceiling. One additional pendant added in the den and the pendant under the stairs has been changed to a sidewall type. No resubmittal needed per Bill Alexander.
FIR05-00478 INSP-Supply line flush8/18/20058/18/20058/18/2005 11:59:32 AMAFAIL
Underground hydro test failed.
MIS05-00127 FIR-Final8/17/20058/18/20058/18/2005 10:53:00 AMAFAIL
brian ###-#### -
Provide annual inspection for fire extinguisher and fire sprinklre system. Repair exit signs/emergency lights. Cover electrical outlets. Remove sprinkler pendant. Remove roofing over office.
FIR05-00346 INSP-Final Inspection8/17/20058/18/20058/18/2005 10:21:04 AMAPASS
fire sprinkler finaled
FIR05-00186 INSP-Final Inspection8/16/20058/18/20058/18/2005 9:32:59 AMACANC
ray; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
FIR05-00185 INSP-Final Inspection8/17/20058/18/20058/18/2005 12:00:00 AM CANC
ray; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
FIR05-00124 INSP-Final Inspection8/18/20058/18/20058/18/2005 12:00:00 AMPFAIL
Maximum head spacing for the attic heads is 120sq. ft. per review note #9. The uprights are overspaced in many locations off the walls in the attic. Upright sprinklers are not sloped with roof deck at the southend of the attic. CPVC piping is not tented correctly in the attic at the central area. Verify that the cpvc piping exposed in the mechanical room can be. Remove switch at the air compressor.